18-HD82D1-1B-EN
SERVICE continued
ABOUT
REMINDERS
Setting Range Description
Filtration Enable [No], Yes Filter change reminder
Filter Period* [Monthly], Quarterly, Bi-Annually,
Annually
Filter change reminder period
Start Month* [Jan], Feb, Mar, Apr, May, Jun,
Jul, Aug, Sep, Oct, Nov, Dec
Period start month
System Maint Enable [No], Yes System Maintenance reminder
Maint Period* [Bi-Annually], Annually Maintenance reminder period
First Maint Month* Jan, Feb, [Mar], Apr, May, Jun,
Jul, Aug, Sep, Oct, Nov, Dec
Period start month
Second Maint Month* Jan, Feb, Mar, Apr, May, Jun, Jul,
Aug, [Sep], Oct, Nov, Dec
2nd period start month
Humidier Enable [Yes], No
Start Month [Jan], Feb, Mar, Apr, May, Jun,
Jul, Aug, Sep, Oct, Nov, Dec
Once all selections have been made, press the Done button to exit and return to menu. Press Next to navigate to the next setting.
Setting Range Description
Version XXXXXX Firmware version number
Device ID (SIN) XXXXXX Unit serial number
ODU Type None, AC, HP Outdoor unit type setting
IDU Type Electric, Gas/Oil, Hydronic Indoor unit type setting
SOV W/Cool, W/Heat Switchover value type setting (HP only)
Once all selections have been made, press the Done button to exit and return to menu. Press Next to navigate to the next setting.
RESTORE DEFAULTS
Setting Action Description
Restore HVAC Defaults Yes, No Resets all HVAC settings to Default Settings
Restore Factory Defaults Press and Hold “Yes” Press and hold “Yes” button until “Factory” is displayed
Resets HVAC and WiFi defaults
The following is a guide of the menu options available on screen accessed by pressing the Menu button. Certain
menu selections, which are marked by an asterisk ( * ), may or may not be present depending on other menu settings.
TEST MODE (stays on for 30 minutes)
Test Mode Settings Description
Blower (Non-VS) Blower On Energize “G” circuit
Blower (VS) 50%, 100% Energize “G” and “BK” circuit
Cooling Single Stage, 1st Stage, 2nd Stage Energize selected “Y1” or “Y2”, “O” and “G” circuit (BK also for VS
indoor unit)
Comp Heating*
Single Stage, 1st Stage, 2nd Stage
Energize selected “Y1” or “Y2” and “G” circuit (“BK” also for VS
indoor unit)
Indoor Heating
Single Stage, 1st Stage, 2nd Stage
Energize selected “W1” or “W2” (“G” circuit also for electric heat)
Aux Relay Relay On Close normally open dry contacts
Once testing is complete, press the Done button to exit and return to menu.
XR724 USER GUIDE