XR724 Control Response Proles
CLEAN SCREEN
Setting Range Description
Clean Screen Yes, No 30 sec countdown
Once all selections have been made, press the Done button to exit and return to menu. Press Next to navigate to the next setting.
From Installer Settings / Comfort Settings (numbers are in degrees, F or C)
Cooling Normal Less Aggressive More Aggressive
Cooling Delta Stage 1 ON 0.5 1 0.5
Cooling Delta Stage 2 ON 1.5 2 1
Cooling Delta Stage 1 OFF -0.5 0 -1.0
Cooling Delta Stage 2 OFF -0.5 0 -1.0
Heating - HP Normal Less Aggressive More Aggressive
Comp Heat Delta Stage 1 ON 0.5 1 0.5
Comp Heat Delta Stage 2 ON 1.5 2 1.0
Indoor Heat Delta Stage 1 ON 2.5 3 1.5
Indoor Heat Delta Stage 2 ON 3.5 4 2.0
Comp Heat Delta Stage 1 OFF 0 0 0
Comp Heat Delta Stage 2 OFF 0 0 0
Indoor Heat Delta Stage 1 OFF 0 0 0
Indoor Heat Delta Stage 2 OFF 0 0 0
Heating - Gas Normal Less Aggressive More Aggressive
Indoor Heat Delta Stage 1 ON 0.5 1 0.5
Indoor Heat Delta Stage 2 ON 1.5 2 1.0
Indoor Heat Delta Stage 1 OFF 0 0 0
Indoor Heat Delta Stage 2 OFF 0 0 0
Timers Normal Less Aggressive More Aggressive
Heat Stage UP Timer 15 min 20 min 10 min
Cool Stage UP Timer 15 min 20 min 10 min
XR724 USER GUIDE