EasyManuals Logo
Home>Trane>Air Conditioner>Precedent

Trane Precedent User Manual

Trane Precedent
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #81 background imageLoading...
Page #81 background image
81RT-PRC006-EN
Table ED-3 — Electrical Characteristics — Evaporator Fan Motors — Direct Drive
Standard Evaporator Fan Motor Oversized Evaporator Fan Motor
Unit Amps Amps
Tons Model No. No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA
Y*C036A1 1 208-230 1 .33 2.30 3.90 1 208-230 1 .50 4.70 9.80
3
Y*C036A3 1 208-230 1 .33 2.30 3.90 1 208-230 1 .50 4.70 9.80
Y*C036A4 1 460 1 .33 1.10 2.00 1 460 1 .50 2.30 5.20
Y*C036AW 1 575 1 .33 1.10 1.80 1 460 1 .50 1.70 3.60
Y*C048A1 1 208-230 1 .60 3.60 6.60 1 208-230 1 .80 5.70 13.60
Y*C048A3 1 208-230 1 .60 3.60 6.60 1 208-230 1 .80 5.70 13.60
4
Y*C048A4 1 460 1 .60 1.70 2.80 1 460 1 .80 3.30 7.20
Y*C048AW 1 575 1 .60 1.50 2.40 1 575 1 .80 2.30 5.80
Y*C060A1 1 208-230 1 .90 6.20 14.0 1 208-230 1 1.00 7.90 16.40
Y*C060A3 1 208-230 1 .90 6.20 14.0 1 208-230 1 1.00 7.90 16.40
5
Y*C060A4 1 460 1 .90 2.90 6.60 1 460 1 1.00 3.20 8.20
Y*C060AW 1 575 1 .90 2.10 4.90 1 575 1 1.00 2.70 5.00
YSC060AK 1 380 1 1.00 4.30 8.30 N/A N/A N/A N/A N/A N/A
Electrical
Data
Table ED-4 — Electrical Characteristics — Evaporator Fan Motors — Belt Drive
Standard Evaporator Fan Motor Oversized Evaporator Fan Motor
Unit Amps Amps
Tons Model No. No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA
3 Y*C036A3 1 208-230 3 1.0 5.0 32.2 ————
Y*C036A4 1 460 3 1.0 2.5 16.1 ————
Y*C036AW 1 575 3 1.0 1.7 13.2 ————
Y*C048A3 1 208-230 3 1.0 5.0 32.2 ————
4 Y*C048A4 1 460 3 1.0 2.5 16.1 ————
Y*C048AW 1 575 3 1.0 1.7 13.2 ————
Y*C060A3 1 208-230 3 1.0 5.0 32.2 ————
5 Y*C060A4 1 460 3 1.0 2.5 16.1 ————
Y*C060AW 1 575 3 1.0 1.7 13.2 ————
YSC060AK 1 380 1 1.0 4.3 8.3 ————
Y*C072A3 1 208-230 3 1.00 5.00 32.20 1 208-230 3 2.00 6.30 48.00
6 Y*C072A4 1 460 3 1.00 2.50 16.10 1 460 3 2.00 3.10 24.00
Y*C072AW 1 575 3 1.00 1.70 13.20 1 575 3 2.00 2.50 18.20
YSC072AK 1 380 3 2.0 4.9 35.0 ————
YSC090A3 1 208-230 3 2.00 6.30 48.00 1 208-230 3 3.00 9.40 83.00
YSC090A4 1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00
YSC090AW 1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00
YSC090AK 1 380 3 2.0 4.9 3.50 1 3.80 3 3.0 6.4 51.1
7½ Y*C092A3 1 208-230 3 2.00 6.30 48.00 1 208-230 3 3.00 9.40 83.00
Y*C092A4 1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00
Y*C092AW 1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00
Y*C102A3 1 208-230 3 2.00 6.30 48.00 1 208-230 3 3.00 9.40 83.00
8½ Y*C102A4 1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00
Y*C102AW 1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00
YSC102AK 1 380 3 2.0 4.9 35.0 1 380 3 3.0 6.4 51.1
Y*C120A3 1 208-230 3 3.00 9.40 83.00 1 208-230 3 5.00 13.40 112.00
10 Y*C120A4 1 460 3 3.00 4.60 42.00 1 460 3 5.00 6.60 56.00
Y*C120AW 1 575 3 3.00 3.70 31.00 1 575 3 5.00 5.40 41.00
YSC120AK 1 380 3 3.0 6.4 51.1 1 380 3 5.0 10.8 66.5
*Indicates both standard and high efficiency airflow.