RTAD-SVX01F-E4 23
General Information
Unit Dimensions
Figure 2 - Unit Dimensions and Minimum Recommended Clearances
Table 24
Note: Size 085 does not exist for Total Heat Recovery option but HE version is available
Unit Dimensions (mm) Minimum clearances (mm)
Length Width Height A B C
Unit Size
Standard, Partial Heat Recovery, and Total Heat Recovery
RTAD 085 3507 2260 2095 1200 1000 1000
RTAD 100-115-125 4426 2260 2095 1200 1000 1000
RTAD 145-150 5351 2260 2115 1200 1000 1000
RTAD 165-180 6370 2260 2215 1200 1000 1000
RTAD 085-100 HE 4426 2260 2095 1200 1000 1000
RTAD 115-125 HE 5351 2260 2115 1200 1000 1000
RTAD 145-150 HE 6370 2260 2215 1200 1000 1000
Free Cooling
RTAD 085 3900 2420 2605 1200 1000 1000
RTAD 100-115-125 4850 2420 2605 1200 1000 1000
RTAD 145-150 5770 2420 2645 1200 1000 1000
RTAD 165-180 6810 2460 2745 1200 1000 1000
RTAD 085-100 HE 4850 2420 2605 1200 1000 1000
RTAD 115-125 HE 5770 2420 2645 1200 1000 1000
RTAD 145-150 HE 6810 2460 2745 1200 1000 1000