Condensate Drain Instructions
The following sections give general instructions for the
installation of the gas furnace condensate drains.
Repositioning of the condensate trap is covered in the
exhaust air options section.
Cutouts with plugs and grommets are provided on the
left and right hand side of the furnace cabinets for drain
connections IN VERTICAL APPLICATIONS. The
standard arrangement is for the drain connection on
the left side. The tubing may have to be trimmed in this
application to avoid kinking.
The uuppffllooww ((vveerrttiiccaall aapppplliiccaattiioonn)) also has provisions
for right side drain connections. Exchange the
grommet and plugs from the left and right side. Trim
all excess tubing to avoid kinking.
It is always recommended that an auxiliary drain pan
be installed under a horizontally installed evaporator or
90% Gas Furnace. Connect the auxiliary drain line to a
separate drain line (no trap is needed in this line).
HHoorriizzoonnttaall aapppplliiccaattiioonnss rreeqquuiirree rreeppoossiittiioonniinngg tthhee
ccoonnddeennssaattee ccaanniisstteerr ttrraapp.. AAddddiittiioonnaallllyy tthhee ddrraaiinn
ttuubbiinngg ccoonnnneecctteedd ttoo tthhee iinndduucceerr hhoouussiinngg mmaayy nneeeedd
ttoo bbee rreeppoossiittiioonneedd ffoorr rreemmoovviinngg tthhee pplluugg aanndd
rreeccoonnnneeccttiinngg tthhee ttuubbiinngg ttoo tthhee lloowweerr ccoonnnneeccttiioonn oonn
tthhee iinndduucceerr hhoouussiinngg..
Connections must be made to an OOPPEENN// VVEENNTTEEDD
DDRRAAIINN.
NNoottee:: All condensate drain piping supplies included
with the furnace are intended for internal piping
only and should not be applied external to the
furnace. All external piping must use 1/2"
minimum size PVC pipe and fittings throughout
for drain connections (fittings, pipe and PVC
solvent cement not provided with furnace, must
be field supplied). A 3/4" coupling is supplied to
connect to systems that are using 3/4" piping
with an air conditioner coil.
NNoottee:: A corrosion resistant condensate pump must be
used if a pump is required for a specific drain
system.
CCAAUUTTIIOONN
WWaatteerr DDaammaaggee//PPrrooppeerrttyy DDaammaaggee!!
IItt iiss rreeccoommmmeennddeedd tthhaatt aa ddrraaiinn ppaann bbee iinnssttaalllleedd
uunnddeerr tthhee ffuurrnnaaccee ttoo pprreevveenntt pprrooppeerrttyy ddaammaaggee oorr
ppeerrssoonnaall iinnjjuurryy ffrroomm lleeaakkiinngg ccoonnddeennssaattee..
IImmppoorrttaanntt:: The condensate drain should be installed
with provisions to prevent winter freeze-up
of the condensate drain line. Frozen
condensate will block drains, resulting in
furnace shutdown. If the drain line cannot
be installed in a conditioned space and/ or
its surrounding ambient temperature is
expected to fall below freezing, then heat
tape should be applied as required to
prevent freezing (per manufacturer’s
instructions). The heat tape should be rated
at 5 or 6 watts per foot at 120 volts. Self-
regulating (preferred) or thermostatically
controlled heat tape is required.
Typical sources of UL listed heat tapes are W.W.
Granger, Inc. (Wintergard PlusTM Series), McMaster
Carr Supply Co. (3554 Series), or your equipment
supplier.
The condensate drain may be cleaned or inspected by
removal of the drain tube at the header.
Evaporator and Furnace condensate drain piping may
be manifolded together. A primary drain vent stack
must be installed and terminated below the outlet of
the secondary heat exchanger drain connection to
prevent water from damaging Furnace controls if the
primary drain outlet plugs up.
WWhheerree tthhee FFuurrnnaaccee iiss iinnssttaalllleedd aabboovvee aa ffiinniisshheedd
cceeiilliinngg,, tthhee pprriimmaarryy ddrraaiinn vveenntt ssttaacckk mmuusstt bbee
iinnssttaalllleedd ssuucchh tthhaatt oovveerrffllooww ffrroomm tthhee vveenntt ssttaacckk
ooppeenniinngg wwiillll ffllooww iinnttoo aann aauuxxiilliiaarryy ddrraaiinn ppaann iinn
oorrddeerr ttoo pprreevveenntt wwaatteerr ddaammaaggee ttoo tthhee ffiinniisshheedd
cceeiilliinngg bbeellooww..
Vertical Applications
Upflow furnace
1. Remove the plug from the side panel where the condensate will
exit.
2. Install the condensate grommet into the side panel.
3. Install the connection tubing from the trap to the side of the unit
and trim all excess tubing to avoid kinks.
Note: For easiest installation, remove the spring clip from the end of
the condensate line and feed through the grommet.
Important: Condensate grommet must be installed for proper
operation.