VAV-SVX08R-EN
11
Digit 16 — Insulation
A = 1/2” Matte-faced
B = 1” Matte-faced
D = 1” Foil-faced
F = 1” Double Wall
G = 3/8” Closed-cell
Digit 17— Motor Type
D = PSC Motor
E = High-efficiency Electronically
Commutated Motor (ECM)
F = Variable Speed High-efficiency
Electronically Commutated Motor (ECV)
Digit 18— Motor Voltage
1 = 115/60/1
2 = 277/60/1
3 = 347/60/1
4 = 208/60/1
5 = 230/50/1
Digit 19— Outlet Connection
1 = Flanged
2 = Slip–and-Drive Connection
Digit 20— Attenuator
0 = None
B = Suppressor
T = Thinline Suppressor
Digit 21— Water Coil
0 = None
1 = 1 Row, Plenum Inlet Installed RH
2 = 2 Row, Plenum Inlet Installed RH
3 = 1 Row, Discharge Installed LH
4 = 1 Row, Discharge Installed RH
5 = 2 Row, Discharge Installed LH
6 = 2 Row, Discharge Installed RH
A = 1 Row Premium, Water Coil Inlet
B = 2 Row Premium, Water Coil Inlet
C = 1 Row Premium, Hot Coil on Discharge LH
D = 1 Row Premium, Hot Coil on Discharge
RH
E = 2 Row Premium, Hot Coil on Discharge LH
F = 2 Row Premium, Hot Coil on Discharge RH
Digit 22— Electrical Connections
F = Flippable Left and Right Hand
L = Left, Airflow hits in face
R = Right, Airflow hits in face
W = Narrow Corridor LH, High Voltage, Inlet
Facing
X = Narrow Corridor RH, High Voltage, Inlet
Facing
Note: Digits W and X, fan-powered series
only.
Digit 23— Transformer
0 = Not Applicable
Digit 24 — Disconnect Switch
0 = None
W = With
Note: Electric reheat w/door interlocking
power disconnect, cooling only and
water reheat w/toggle disconnect.
Digit 25 — Power Fuse
0 = None
W = With
Digit 26 — Electric Heat Voltage
0 = None
A = 208/60/1
B = 208/60/3
C = 240/60/1
D = 277/60/1
E = 480/60/1
F = 480/60/3
G = 347/60/1
H = 575/60/3
J = 380/50/3
K = 120/60/1
Note: Digit K not available wit low height.
Digit 27, 28, 29— Electric Heat kW
000 = None
010 = 1.0 kW
015 = 1.5 kW
460 = 46.0 kW
Notes:
• 0.5 to 8.0 kW in 1/2 kW
increments
• 8.0 to 18.0 kW in 1 kW
increments
• 18.0 to 46.0 kW in 2 kW
increments
Digit 30 — Electric Heat Stages
0 = None
1 = 1 Stage
2 = 2 Stages Equal
3 = 3 Stages Equal
Note: Digit 3 not available with low height.
Digit 31 — Electric Heat Contactors
0 = None
1 = 24V Magnetic
5 = 0-10 Vdc SCR Heat; UC400
6 = 0-10 Vdc SCR Heat; FMTD/ENCL/DD00
7 = 24V SSR (Solid State Relay)
Notes: SCR cannot be selected with the
following:
• kW>10,208V, 3Ph, Low Height
• kW>22,480V, 3Ph, Low Height
• Voltage = 575V
Digit 32— Air Switch
0 = Not Applicable
W = With
Digit 33— Not Used
0 = Not Applicable
Digit 34 — Actuator
0 = Standard
A = Belimo™ Actuator
G = Trane Analog Actuator (UC210 or UC400
only)
Digit 35 — Wireless Sensors
0 = None
3 = Trane Air-Fi® Wireless Communications
Interface
Note: All sensors selected in accessories.
Digit 36 — Pre-wired Factory
Solutions
0 = None
1 = Factory-mounted DTS
2 = HW Valve Harness
3 = Both DTS/HW Valve Harness
Digit 37 — Bottom Access
0 = None
W = Access Left Side Terminal Unit
Digit 38 —Piping Package
0 = None
A = 2–Way Automatic Balancing
B = 3–Way Automatic Balancing
C = 2-Way Standard Valve Only, Floating
Point Actuator
D = 3-Way Standard Valve Only, Floating
Point Actuator
E = 2-Way Standard Valve Piping Package,
Floating Point Actuator
F = 3-Way Standard Valve Piping Package,
Floating Point Actuator
MMooddeell NNuummbbeerrss