Maintenance
Periodic maintenance of the VariTrane product is
minimal, but necessary for efficient operation. Routine
maintenance consists of inspecting/replacing the air
filters of the fan-powered terminals.
Motors
Both the Permanent Split Capacitor( PSC) and the
Electrically Commutated Motor (ECM) require no
lubrication during its normal life of operation.
Fan Wheel
Routinely inspect the fan wheel for dirt or debris and
cleaned as necessary.
Filter
Routinely inspect and/or replace the filter on fan-
powered terminals depending on the environmental
conditions of the plenum.
Filter Change Out
To remove the filter, turn each of the filter retaining
clips 90° (CW or CCW)
Remove the filter and replace with new filter of the
same frame size.
Return the filter clips to their retaining position by
turning them 90° (CW or CCW) back to their original
position.
Water Coil
Periodically inspect water coils and clean fins.
Water coils are provided with an access panel as
standard to assist with inspection and cleaning.
Fan Motor Replacement
WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee ww//CCaappaacciittoorrss!!
FFaaiilluurree ttoo ddiissccoonnnneecctt ppoowweerr aanndd ddiisscchhaarrggee
ccaappaacciittoorrss bbeeffoorree sseerrvviicciinngg ccoouulldd rreessuulltt iinn ddeeaatthh oorr
sseerriioouuss iinnjjuurryy..
DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee
ddiissccoonnnneeccttss aanndd ddiisscchhaarrggee aallll mmoottoorr ssttaarrtt//rruunn
ccaappaacciittoorrss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr
lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr
ccaannnnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd.. FFoorr vvaarriiaabbllee
ffrreeqquueennccyy ddrriivveess oorr ootthheerr eenneerrggyy ssttoorriinngg
ccoommppoonneennttss pprroovviiddeedd bbyy TTrraannee oorr ootthheerrss,, rreeffeerr ttoo
tthhee aapppprroopprriiaattee mmaannuuffaaccttuurreerr’ss lliitteerraattuurree ffoorr
aalllloowwaabbllee wwaaiittiinngg ppeerriiooddss ffoorr ddiisscchhaarrggee ooff
ccaappaacciittoorrss.. VVeerriiffyy wwiitthh aa CCAATT IIIIII oorr IIVV vvoollttmmeetteerr
rraatteedd ppeerr NNFFPPAA 7700EE tthhaatt aallll ccaappaacciittoorrss hhaavvee
ddiisscchhaarrggeedd..
Figure 47. Standard motor removal
Standard height fan-powered series and parallel fan
motors are replaceable through the filter opening and
the standard sliding side access panel. To access the
fan motor, the fan housing must be detached by
removing the mounting bolts that hold the housing to
the fan board. Removing the entire housing allows the
fan motor, fan housing, and fan wheel to be re-aligned
on a workbench or floor and prevent any possible fan
wheel rubbing that may occur. Removing the housing
will provide access to the motor shaft set screw that
holds the fan wheel to the motor shaft.
The low height fan assembly has been designed to be
removed and replaced as a complete unit.