Installation
Space Temperature Averaging
Space temperature averaging is accomplished by wiring a number of remote
sensors in a series/parallel circuit.
Using the BAYSENS016* or BAYSENS017*, at least four sensors are required to
accomplish space temperature averaging. Example #1 illustrates two series
circuits with two sensors in each circiut wired in parallel. The square of any
number of remote sensors is required. Example #2 illustrates three sensors
squared in a series/parallel circuit. Using BAYSENS032*, two sensors are
required to accomplish space temperature averaging. Example #3 illustrates the
circuit required for this senor. Tab l e 4 lists the temperature versus resistance
coefficient for all sensing.