Part Two
18
Symptom
Possible Cause
Corrective Action
Monitor does not
respond to RS-
485
communications.
Network protocol
is incorrect.
Incorrect network
address.
Incompatible
software.
Go into CONFIGURE menu, RS-485 type item. The
protocol must match host system. Select correct
interface.
The network address at the building automation system
and at the monitor must match. The network address
must be unique for each monitor.
Data sent to monitor may be in form that the EverWatch
monitor cannot recognize.