6.2.1 FST error and warning parameters
The error parameters are automatically set during auto calibration but can be manually adjusted
through ValConnect or the display.
For the full stroke the error parameters are set to the following values:
Breakaway timeout = Reference breakaway time + Reference FST time
FST timeout = Reference total time
Total timeout = 2 * Reference total time
Minimum breakaway pressure = Reference pressure at 50%
The Start pressure error limits are not set automatically and function is disabled.
The full stroke warning parameters are set to the following values:
Low breakaway time = Reference breakaway time 50%
High breakaway time = Reference breakaway time + 50%
Low breakaway pressure = Reference breakaway pressure 50%
High breakaway pressure = Reference breakaway pressure + 50%
Low fail position stroke time = Reference fail position stroke time 50%
High fail position stroke time = Reference fail position stroke time + 50%
½
Figure 14: Breakaway timeout

Other manuals for Val Controls IDC24-AF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Val Controls IDC24-AF and is the answer not in the manual?

Val Controls IDC24-AF Specifications

General IconGeneral
BrandVal Controls
ModelIDC24-AF
CategoryController
LanguageEnglish

Related product manuals