8.3 Full stroke errors (451 to 468)
No. 451
FST start condition: Not at operational
Description
The valve is not at the operational position
Trouble shooting
This error can be solved by
Make sure the valve is at the operational position
Perform an endpoint calibration.
Increase the full stroke position deadband
No. 452
FST start condition: Low start pressure
Description
The measured pressure is below Start pressure low
Trouble shooting
This error can be solved by:
Increase the pressure in the hydraulic/pneumatic system
Decrease the Start pressure low value
No. 453
FST start condition: High start pressure
Description
The measured pressure is above Start pressure high
Trouble shooting
This error can be solved by:
Increase the pressure in the hydraulic/pneumatic system
Increase the Start pressure high value
No. 454
FST start condition: In ESD mode
Description
Emergency shutdown is detected
Trouble shooting
This error can be solved by:
Activate the ESD input
No. 456
Aborted by the user
Description
The test was aborted by the user
Trouble shooting
This error can be solved by:
Perform a new FST

Other manuals for Val Controls IDC24-AF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Val Controls IDC24-AF and is the answer not in the manual?

Val Controls IDC24-AF Specifications

General IconGeneral
BrandVal Controls
ModelIDC24-AF
CategoryController
LanguageEnglish

Related product manuals