Vertiv | NetSure Rectifier Module User Manual (UM1R483500e) | Rev. R
• Typical Input Data (1R484000e): 60 Hz input.
a) System output is initially adjusted to 53.5 VDC as measured at the system sense points at 50 % of
full load and nominal input. “Percent of Full Load” refers to percent of 74.7 amperes.
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat
Dissipation
BTU/Hr
208
70 14.312 2958.40 2952.19 0.998 94.47 557.1881
100 20.885 4298.34 4292.11 0.998 92.73 1064.971
240
30 5.324 1279.22 1251.30 0.978 95.62 187.0544
80 14.152 3379.85 3370.42 0.997 94.54 628.0714
100 17.915 4266.63 4258.59 0.998 93.46 950.5522
277
80 12.201 3372.95 3355.44 0.995 94.96 577.1815
b) Maximum Input Current: at 100% of full load with output adjusted to 58 VDC as measured at the
shelf output terminals.
Nominal Input
Voltage
Input
Voltage
Input Current
(Amperes)
208/240 204 21.0