• Typical Input Data (1R483500e): 60 Hz input.
a) System output is initially adjusted to 54.48 VDC as measured at the system sense points at 50 % of
full load and nominal input. “Percent of Full Load” refers to percent of 60 amperes.
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat
Dissipation
BTU/Hr
208
75 12.34 2553 2546 0.997 95.48 378.6
120 18.36 3790 3782 0.998 93.29 854.6
240
25 3.66 877 850 0.969 95.59 123.2
100 14.34 3423 3414 0.997 94.90 576.4
120 15.79 3768 3757 0.997 93.91 765.4
277
100 12.26 3394.5 3388.8 0.998 94.94 584.78
b) Maximum Input Current: at 100% of full load with output adjusted to 58 VDC as measured at the
shelf output terminals.
Nominal Input
Voltage
Input
Voltage
Input Current
(Amperes)
208/240/277 176 21.60