Vertiv | NetSure Rectifier Module User Manual (UM1R483500e) | Rev. R
• Typical Input Data (1R483200e): 60 Hz input.
a) System output is initially adjusted to 54.48 VDC as measured at the system sense points at 50 % of
full load and nominal input. “Percent of Full Load” refers to percent of 55 amperes.
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat
Dissipation
BTU/Hr
208Vac
(60Hz)
75 11.2183 2325.1 2323.2 0.999 95.23 378.51
120 16.5356 3419 3418.3 0.999 93.91 710.44
240Vac
(60Hz)
25 3.2515 780.2 772.1 0.990 95.74 112.17
100 12.963 3103.8 3100.5 0.999 94.92 537.14
120 14.2234 3402.7 3399.9 0.999 94.50 638.09
b) Maximum Input Current: at 100% of full load with output adjusted to 58 VDC as measured at the
shelf output terminals.
Nominal Input
Voltage
Input
Voltage
Input Current
(Amperes)