Vertiv | NetSure Rectifier Module User Manual (UM1R483500e) | Rev. R
• Typical Input Data (1R483200): 60 Hz input.
a) System output is initially adjusted to 54.48 VDC as measured at the system sense points at 50 % of
full load and nominal input. “Percent of Full Load” refers to percent of 55 amperes.
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat
Dissipation
BTU/Hr
208
75 11.87 2457 2453 0.998 91.6 701.88
120 16.88 3478 3477 0.998 89.9 1208.42
240
25 3.65 865 846 0.977 88.7 325.42
100 13.68 3269 3265 0.998 91.8 917.81
120 14.46 3455 3454 0.998 90.5 1118.21
b) Maximum Input Current: at 100% of full load with output adjusted to 58 VDC as measured at the
shelf output terminals.
Nominal Input Voltage Input Voltage Input Current (Amperes)
208/240 176 20.42