EasyManuals Logo

Viessmann VITOTRONIC 100 User Manual

Viessmann VITOTRONIC 100
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #43 background imageLoading...
Page #43 background image
43
Cause Remedy
The heating system is switched off.
Turn on the ON/OFF switch (see page 41).
Switch ON the mains isolator if installed (outside the
boiler room).
Set the MCB in the power distribution board (main do-
mestic MCB).
Control unit incorrectly adjusted.
The remote control (if installed) is set incorrectly.
Separate operating instructions
Central heating must be set.
Check the settings and correct if required:
Operating program (see page 17)
Room temperature (see page 22)
Time (see page 31)
Time program, central heating (see page 23)
Heating curve (see page 23)
The DHW cylinder is being heated. Wait until the DHW cylinder has been heated up.
Reduce the DHW draw-off rate or temporarily reduce
the DHW temperature as required.
No fuel. With oil or LPG:
Check the fuel reserves and re-order if required.
With natural gas:
Open the gas shut-off valve. If necessary, check with
your gas supply utility.
"Fault" is displayed. Check what type of fault it is. Acknowledge the fault
(see page 38). If necessary, notify your contractor.
"Burner fault" is displayed.
Vitotronic 300, type CM1E and Vitotronic 100,
type CC1E:
Press the burner reset button.
See separate boiler or burner instructions.
Vitotronic 300, type CM1I and Vitotronic 100,
type CC1I:
Follow the instructions on the display: See page 38.
Contact your contractor if the burner still fails to start.
Danger
If faults are not rectified, they can have life
threatening consequences.
Do not acknowledge fault messages several
times in quick succession. Notify your contractor
if a fault recurs. Your contractor will be able to
analyse the cause and rectify the fault.
"Screed drying" is activated. No action required.
The set operating program will be enabled once the
screed drying time has elapsed.
The mixer motor is faulty. Notify your heating contractor.
What to do if...
Rooms are too cold
5863758

Other manuals for Viessmann VITOTRONIC 100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Viessmann VITOTRONIC 100 and is the answer not in the manual?

Viessmann VITOTRONIC 100 Specifications

General IconGeneral
DisplayLCD
ProgrammingProgrammable
Temperature ControlYes
CompatibilityViessmann heating systems
TypeElectronic control unit
ApplicationHeating systems
Operating Voltage230 V AC
Protection ClassIP20
Weight0.5 kg
Control FunctionsHeating circuit control
Control TypeWeather-compensated control

Related product manuals