Chapter 6. Appendix
Specifications
MODEL
8kVA
10kVA
SINGLE PHASE
3-PHASE
INPUT
Voltage (Vac)
160Vac~280Vac
277Vac~485Vac
Frequency (Hz)
50 / 60 ±10%
Phase
Single
3-PHASE
Input Power Factor
> 0.95
OUTPUT
Voltage (Vac)
208/220/230/240
Capacity
8Kva/6.4Kw
10Kva/8Kw
Wave Form
Sine Wave
Voltage Regulation
±2%
Frequency Stability
±0.5Hz (Free Running)
Crest Factor
3 : 1
Transfer Time
(Line Fault)
0 ms
Efficiency (AC to AC)
> 85%
DC Start
Yes
BATTERY
Type
Sealed Maintenance Free Lead Acid
Quantity (pcs)
16
Voltage (Vdc)
192
Recharge Time
8 Hours to 90%
Supplementary
Charger
(Optional)
2000W Charger for extended back-up application
DISPLAY
LED
Utility, Inverter, and Fault Conditions
LCD (Optional)
Input Voltage, Output Voltage, Output Frequency, Load Percentage, Inner
Ambient Temperature, Battery Voltage and status, Input Phase Error or
Ground Fault, Fault Conditions