10
BURNER MOTOR WILL
NOT RUN (CONT.)
Faulty oil primary control. (Applicable
only if burner comes with ignition
control).
Observe burner sequence of operations. Replace control if
necessary
BURNER STAYS ON
WHEN NO CALL FOR
HEAT
Check for proper operation, replace if necessary.
BURNER DOES NOT LIGHT, 12Vdc WAYNE OIL PRIMARY CONTROL REMAINS ON STANDBY
1. Make sure flow switch is closed
2. Check for 13.5Vdc voltage at
primary control.
Check battery voltage while equipment is
running. There should be 14 volts or higher at the
battery and investigate equipment wiring for any
crack or tears in the wire insulation.
3. Check LED light on 101382
control
101382 red LED flashes for 2 seconds followed
by one short 0.5 second flash
Sees external light during safety check or
connections are shorted.
4. Shield cad cell from external light
Identify control model number. Energize white
thermostat wire to verify that burner goes through
proper sequence of operations.
If burner does not light, replace primary control.
NOTE: This section refers to Wayne 101382 series controls.
Troubleshooting tables on pages 10-12 are specific to burners that
come equipped with an oil primary control. These sections only
apply if the general troubleshooting guide instructs the licensed
contractor to consult these sections while servicing the burner.