EasyManuals Logo
Home>Worcester>Boiler>C1

Worcester C1 User Manual

Worcester C1
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
31
Fan overrun
function active
for 3 minutes
OVERRUN FUNCTION
Above
9°C
Commence normal
central heating mode
until temperature
reaches 30°C
5°C
to
9°C
Below
5°C
No demand
and primary
temperature
below 8°C
Internal
“Autofrostat”
demand
Wait in normal
off state for
30 minutes
Run pump for
four minutes
Monitor
central
heating
sensor
Return to
normal off
state
AUTOFROSTAT FUNCTION
Run pump
20°C
END DHW
DEMAND
END CH
DEMAND
If primary temp
over 85° pump
cycles for 2
seconds every 10
seconds until
temp below
85°
Pump runs for
3 minutes
If primary temp
above 80° fan
runs until temp
below 80°C
(35 seconds
minimum)
If primary temp
below 80° run
fan for 35
seconds
After 3 minutes the pump runs if:
primary temp over 95° until below 77°
hot water temp over 98° until below 63°
If primary rises
above 85° fan
runs until temp
falls below 80°

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Worcester C1 and is the answer not in the manual?

Worcester C1 Specifications

General IconGeneral
BrandWorcester
ModelC1
CategoryBoiler
LanguageEnglish

Related product manuals