6 SPECIFICATIONS
51
6.4 BRAKING UNIT SPECIFICATIONS
* Loading time rate can be used below 10% ED (max. 10 sec.)
Braking Unit Model
CDBR-
200V to 300V 380V to 460V 500V to 575V
2015
B,
2015
C
2022
B,
2022
C
2045
B
2110
B
4030
B
4045
B
4090
B
4220
B
5037
B
5110
B
5300
B
Applicable Motor Output HP
(kW)
20
(15)
30
(22)
60
(45)
150
(110)
40
(30)
60
(45)
120
(90)
300
(220)
57
(37)
150
(110)
400
(300)
Output
charac-ter-
istics
Max. Discharge
Current(A) (peak
value) *
40 60 100 250 40 60 100 250 40 100 250
Rated Discharge
Current (A)
15 20 30 80 15 18 30 80 15 30 80
Braking Start
Voltage
330/345/365/380V±3V 630/660/690/730/760V ±6V 825V/ 950V ±8V
Max. Hysteresis
Error
Approx. 8V Approx. 16V Approx. 20V
Power
Supply
VDC
243 (1.35
×200×0.9) to
400V peak
460 (1.35×380×0.9) to
800V peak
607 (1.35×500×0.9)
to 1000V
Protec-
tive
Func-
tions
Fin Overheat
Thermostat
Power Charge
Indication
Charge lamp stays ON until bus voltage drops below 50V.
Envion-
mental
Condi-
tions
Location
Indoor (protected from corrosive gases and dust)
Altitude
1000m max.
Ambient
Temperature
+14 to 104°F (-10 to +40°C) (not frozen)
Storage Transpor-
tation Tempera-
ture
-4 to 140°F (-20 to +60°C)
Humidity
90%RH (non-condensing)
Vibration
1G at 10 to less than 20Hz, up to 0.2G at 20 to 50 Hz
Protective Configuration
Wall-mounted enclosed type
Heat Loss (W)
32 38 31 64 54 59 35 71 22 53 116