10 Attachment
290 YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
Model Terminal
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening
Torque
Nm (inlb)
Size Shape
B018
L/L1, N/L2 6 2.5 - 10 10 M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
-, +1 6 2.5 - 10 10 M4
1.5 - 1.7
(13.5 - 15)
B1, B2 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
6
*2
4 - 10
*2
- M5
2.0 - 2.5
(17.7 - 22.1)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-
loop crimp terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of
10 mm
2
(copper wire).
8-4NS from JST Mfg. Co., Ltd.
R8-4S from NICHIFU Co.,Ltd.

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals