10 Attachment
YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction 307
Model Terminal
Recommen
ded Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening
Torque
N∙m (in∙lb)
Size Shape
4044
R/L1, S/L2, T/L3 4 10 - 2 18 M5
• ≤ AWG 10
2.3 - 2.5
(19.8 - 22)
• AWG 8 ≤
4.1 - 4.5
(36 - 40)
U/T1, V/T2, W/T3 6 12 - 4 18 M5
• ≤ AWG 10
2.3 - 2.5
(19.8 - 22)
• AWG 8 ≤
4.1 - 4.5
(36 - 40)
-, +1, +2 2 8 - 2 18 M5
4.1 - 4.5
(36 - 40)
B1, B2 8 12 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
6 10 - 6 - M6
5.4 - 6.0
(47.8 - 53.1)
4060
R/L1, S/L2, T/L3 2 8 - 2 18 M5
4.1 - 4.5
(36 - 40)
U/T1, V/T2, W/T3 4 10 - 2 18 M5
• ≤ AWG 10
2.3 - 2.5
(19.8 - 22)
• AWG 8 ≤
4.1 - 4.5
(36 - 40)
-, +1, +2 2 6 - 2 18 M5
4.1 - 4.5
(36 - 40)
B1, B2 8 12 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
6 10 - 6 - M6
5.4 - 6.0
(47.8 - 53.1)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-
loop crimp terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of
10 mm
2
(copper wire).
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.