1. Explosion Protection Instrumentation
1-4
TI 32S01J30-01E
1.3 Overview of Connection to the Devices
Installed in a Hazardous Area
This section describes the overview of connection to the devices installed in a hazardous
area, giving some examples
Connection of FIO equipment for ATEX, IECEx, and UKEX
ProSafe-RS/ProSafe-RS Lite Ex “ec”/Type “n” compliant equipment can be connected to the
intrinsic safety equipment installed in Zone 0, Zone 1 and Zone 2 using a safety barrier and
explosion-proof wiring as shown in the following gures.
ProSafe-RS/ProSafe-RS Lite equipment can be connected to the Ex “ec”/Type “n” devices
installed in Zone 2 with explosion-proof wiring that is dened in IEC/EN 60079-14 and the rules/
standards of each country or region.
ProSafe-RS/ProSafe-RS Lite equipment can be connected to the ameproof devices installed
in Zone 1 / Zone 2 with explosion-proof wiring that is dened in IEC/EN 60079-14 and the rules/
standards of each country or region. (*1)
*1: SCB100 / SCB110 shall not be installed in Zone 1.
When using SCB100/SCB110 to perform eld wiring diagnosis to the eld device installed in Zone 1, it is necessary to prepare
an element that has the same characteristics as SCB100/SCB110 and is compatible with Zone 1 installation. When using these
elements to realize the wiring diagnosis of the DI function, check the behavior with the actual connection environment before
using. Please contact with Yokogawa about the specication of SCB100/SCB110.
Zone 1 Zone 2 Non-Hazardous Area
Flameproof
device
Zone 0
Intrinsic safety
device
SNU
Intrinsic safety
device
Ex "ec"
Type “n”
device
*1
*1
*1
Intrinsic safety
device
*1
F010301E.ai
Safety
Barrier
Safety
Barrier
Safety
Barrier
*1
*1: Explosion-proof wiring that is dened in IEC/EN 60079-14 or the rules/standards of each country or region.
Figure Ex “ec”/Type “n” (Installation in Non-Hazardous Area)
Dec 3, 2021-00

Table of Contents

Other manuals for YOKOGAWA ProSafe-RS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ProSafe-RS and is the answer not in the manual?

YOKOGAWA ProSafe-RS Specifications

General IconGeneral
BrandYOKOGAWA
ModelProSafe-RS
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals