2. Explosion Protection Instrumentation in Zone 2/Division 2
2-11
TI 32S01J30-01E
2.2 Ex “ec”, Type “n”
Ex “ec”/Type “n” is a construction to enhance safety where spark, arc or high surface temperature
is not caused in a normal operation and is avoided under dened conditions such as overload.
Explosion-proof specications, Complied standard, and Compliant
Products
The ProSafe-RS/ProSafe-RS Lite safety unit, safety node unit, I/O modules and optical repeater
comply with the following standards.
ATEX Ex “ec”, ATEX Type “n”
The references are listed in the following table.
Explosion protection construction
Reference of Explosion-proof specications,
Complied Standard, and Compliant Products
SSSC60
SSC50
SSC57
L1SC70
S2SC70
FIO Node
Unit
N-IO Node
Unit
N-IO eld
enclosure
S2BN4D S2BN5D
ATEX Ex “ec” (*1) App. 2.1 App. 2.2 App. 2.1 App. 2.2 App. 2.3 App. 2.5
ATEX Type “n” App. 2.4
–: Non-compliant
Note: Regarding the latest conformity standard, refer to the GS 32P01B60-01EN “Standards Compliant Models”
*1: *1: The following products that use sealed devices have also comply with ATEX Type “nC”.
S2SC70, SSC60, SSC50, SSC57, L1SC70, SNB10D, L1NB10D, SBD2D, SBD3D, SBD4D, S1BB4D, S2ZN70D, and
S2ZN60D.
ProSafe-RS/ProSafe-RS Lite equipment and an optical repeater can be installed in Zone 2
hazardous area if they are placed in a keyed cabinet (*6) with protection rating IP54 or higher.
The I/O module can be connected to an intrinsic safety eld device installed in Zone 0, Zone
1 and Zone 2 hazardous area using a safety barrier. In addition, it is possible to connect
ProSafe-RS/ProSafe-RS Lite equipment installed in a non-hazardous area and an intrinsic safety
eld device installed in Zone 0, Zone 1 and Zone 2 hazardous area using a safety barrier.
IECEx Ex “ec”, IECEx Type “n”
The references are listed in the following table.
Explosion protection construction
Reference of Explosion-proof specications,
Complied Standard, and Compliant Products
SSSC60
SSC50
SSC57
L1SC70
S2SC70
FIO Node
Unit
N-IO Node
Unit
N-IO eld
enclosure
S2BN4D S2BN5D
IECEx Ex “ec” (*1) App. 1.2 App. 1.1 App. 1.2 App. 1.3 App. 3.2
IECEx Type “n” App. 3.1
–: Non-compliant
Note: Regarding the latest conformity standard, refer to the GS 32P01B60-01EN “Standards Compliant Models”
*1: The following products that use sealed devices have also comply with IECEx Type “nC”.
S2NN70D and S2NN60D
Apr. 25, 2022-00

Table of Contents

Other manuals for YOKOGAWA ProSafe-RS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ProSafe-RS and is the answer not in the manual?

YOKOGAWA ProSafe-RS Specifications

General IconGeneral
BrandYOKOGAWA
ModelProSafe-RS
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals