2. Explosion Protection Instrumentation in Zone 2/Division 2
2-2
TI 32S01J30-01E
Precautions
To install a device in accordance with the standards above, the device needs to be
accommodated in a keyed metal cabinet and installed. As for US (FM), it is necessary to use
a cabinet complying with FM Class 3810 and FM Class 3600 or approved by FM or local
testing authorities for explosion-proof products.
As for Canada (FM), it is necessary to use a cabinet approved by CSA or local testing
authorities for explosion-proof products. (*1)
As a rule, NI explosion protection where FM approved device is connected to CSA approved
device shall not be approved. It is necessary to connect devices approved by the same
standard.
Installation, wiring and maintenance of the devices should be carried out by the engineers or
other professional personnel with related expertise.
The Installation and the wiring should be in accordance with NEC (the National Electrical
Code : ANSI/NFPA-70), CEC (Canadian Electrical Code) or wiring construction standards of
the countries or regions where wiring is laid.
During installation, the venting slots of the devices must not be blocked by cable parts, xing
accessories, etc. (*1)
When the devices are used, abide by the following guidance so as to ensure the safety and
performance.
- Make sure that the door of the cabinet is closed when the devices are running.
- Make sure that all the empty slots in the cabinet should be properly covered with attached
caps.
- Make sure that all the cables are rigidly xed in the cabinet.
- Make sure that the breakers are in the power supply circuits located in non-hazardous
areas so that the power can be shuto󰀨 when abnormality occurs.
Both the initial and periodical inspection should be based on the regulations of IEC 60079-
17 and carried out by the personnel who have received the professional training.
Instructions provided in GS (General specications), TI (Technical Information of Installation
Guidance) and/or IM (User’s Manuals) shall be observed.
As for the precautions of N-IO eld enclosure, refer to Appendix 1.3 US (FM) NI/Canada
(FM) NI/IECEx Ex “ec” Control Drawing of N-IO eld enclosure.
Please observe the following precautions while product is operating or under maintenance
service.
*1: Excluding N-IO eld enclosure.
WARNING
WARNING -EXPOSURE TO ANY CHEMICALS MAY DEGRADE THE SEALING PROPERTIES
OF MATERIALS USED IN THE FOLLOWING DEVICES ; SBD2D, SBD3D, SBD4D and
S1BB4D.
Dec. 3, 2021-00

Table of Contents

Other manuals for YOKOGAWA ProSafe-RS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ProSafe-RS and is the answer not in the manual?

YOKOGAWA ProSafe-RS Specifications

General IconGeneral
BrandYOKOGAWA
ModelProSafe-RS
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals