Dec. 3, 2021-00
Yokogawa Electric Corporation
Model
ProSafe-RS/ProSafe-RS Lite
Title
Control drawing
No.
NFM014-A13
Page
1
Revision
78
Date
2021-04-28
Revised pages
1−4, 8−12, 16, 17
(US)
■ Applicable standards:
FM 3600:2018
FM 3611:2018
FM 3810:2018
ANSI/UL 121201 Ed. 9 (2019)
ANSI/UL 61010-1 Ed. 3 (2012)
ANSI/UL 61010-2-030 Ed. 1 (2012)
ANSI/UL 61010-2-201 Ed. 1 (2014)
The models which conform to these standards are listed in the following tables of the ambient
temperature ranges.
■ Markings:
CL I DIV 2 GP ABCD T4
■ Specific Conditions of Use:
– The equipment shall be installed in a lockable metal cabinet. The suitability of the installation
shall be determined by the authority having jurisdiction.
– The Ambient Temperature ranges are as follows.
Classifications
Model
Ambient Temperature (*1)
Safety Control Units
for Vnet/IP
SSC50S-S2E
□□
−20 to 40 °C (*2)
SSC50S-F2E□□
−20 to 70 °C (*3)
SSC50D-S2E□□
−20 to 40 °C (*2)
SSC50D-F2E□□ −20 to 70 °C (*3)
SSC57S-S2E□□
−20 to 40 °C (*2)
SSC57S-F2E□□
−20 to 70 °C (*3)
SSC57D-S2E□□
−20 to 40 °C (*2)
SSC57D-F2E□□
−20 to 70 °C (*3)
SSC60S-S2E□□
−20 to 40 °C (*2)
SSC60S-F2E□□ −20 to 70 °C (*3)
SSC60D-S2E□□
−20 to 40 °C (*2)
SSC60D-F2E□□
−20 to 70 °C (*3)
Safety Node Units
SNB10D-
□1E
SNB10D-
□2E
SNB10D-
□4E
−20 to 70 °C (*3)
Unit for Optical Bus
Repeater Module
SNT10D-21E
SNT10D-22E
SNT10D-24E
−20 to 70 °C