550.13-TG2Y (799)
16 Unitary Products Group
TABLE 17: L*EU480 SUPPLY AIR BLOWER PERFORMANCE
RPM
CFM
SP
1
BHP
2
K
W
SP
1
BHP
2
K
W
SP
1
BHP
2
K
W
SP
1
BHP
2
K
W
SP
1
BHP
2
K
W
12,800 14,400 16,000 17,600 19,200
600
0.31 4.3 3.7 0.13 5.1 4.4 —————————
640
3
0.49 4.8 4.1 0.31 5.6 4.8 0.15 6.3 5.4 ——————
700
0.76 5.5 4.7 0.59 6.4 5.5 0.42 7.2 6.2 0.24 8.1 7.0 0.03 9.2 7.9
775
4
5
1.10 6.5 5.6 0.96 7.4 6.4 0.80 8.4 7.2 0.63 9.4 8.1 0.42 10.4 9.0
800
1.22 6.8 5.9 1.08 7.8 6.7 0.93 8.8 7.6 0.76 9.8 8.4 0.55 10.8 9.3
900
1.76 8.1 7.0 1.64 9.3 8.0 1.50 10.5 9.0 ——————
915
6
1.84 8.3 7.2 1.72 9.5 8.2 1.58 10.7 9.2 ——————
1.
Unit resistance is based on a wet evaporator coil and clean filters.
2.
Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the
blower motor and drive table and the accessory static resistance table for additional information.
3.
Min. speed for drive accessory 1LD0409.
4.
Min. speed for drive accessory 1LD0410.
5.
Max. speed for drive accessory 1LD0409.
6.
Max. speed for drive accessory 1LD0410.