550.13-TG2Y (799)
18 Unitary Products Group
TABLE 18: L*EU600 SUPPLY AIR BLOWER PERFORMANCE
1
RPM
CFM
SP
2
BHP
3
K
W
SP
1
BHP
2
K
W
SP
1
BHP
2
K
W
SP
1
BHP
2
K
W
SP
1
BHP
2
K
W
16,000 18,000 20,000 22,000 24,000
600
0.92 6.0 5.2 0.72 7.2 6.2 0.50 8.4 7.2 0.25 9.7 8.4 ———
660
4
1.27 7.3 6.3 1.09 8.5 7.3 0.88 9.8 8.5 0.62 11.2 9.7 0.33 12.7 11.0
700
1.50 8.2 7.1 1.34 9.4 8.1 1.13 10.7 9.2 0.87 12.2 10.5 0.59 13.7 11.8
760
5
1.86 9.5 8.2 1.72 10.8 9.3 1.53 12.3 10.6 1.28 13.8 11.9 1.00 15.6 13.5
800
6
2.10 10.4 9.0 1.98 11.8 10.2 1.79 13.3 11.5 1.55 14.9 12.9 1.28 16.9 14.6
900
2.70 12.8 11.0 2.62 14.5 12.5 2.50 16.0 13.8 ——————
930
7
2.88 13.5 11.6 2.81 15.3 13.2 —————————
1.
Unit resistance is based on a wet evaporator coil and clean filters.
2.
Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the
blower motor and drive table and the accessory static resistance table for additional information.
3.
Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heat-
ing device. Units with steam or hot water coils are the only exception. On theses units, the BHP must not exceed the nominal HP
rating of the motor.
4.
Min. speed for drive accessory 1LD0411.
5.
Min. speed for drive accessory 1LD0412.
6.
Max. speed for drive accessory 1LD0411
7.
Max. speed for drive accessory 1LD0412.