351579-YTS-B-0608
16 Johnson Controls Unitary Products
Table 5: Settable System Parameters
Address Function Unit Range Default Your Settings
1 Run test ON-OFF OFF
2 Fan on delay-Heating Sec 0-30 30
3 Fan off delay-Heating Sec 0-255 60
4 Fan on delay-Cooling Sec 0-30 0
5 Fan off delay-Cooling Sec 0-255 30
6 Factory setting - - 1 Do not change
7 Suspend Cont Fan when starting Heating ON-OFF OFF
8 Construction Mode - ON-OFF OFF
9 Unoccupied Override Time Period Minutes 0-240 60
10 Occupied Cooling Setpoint °F 45-99 72
11 Occupied Heating Setpoint °F 45-99 68
12 Unoccupied Cooling Setpoint °F 45-99 85
13 Unoccupied Heating Setpoint °F 45-99 60
14 SAT Control-Cooling ON-OFF ON-OFF ON
15 Cooling SAT Control Setpoint °F 40-65 50
16 SAT Control for Heating ON-OFF ON-OFF ON
17 Heating SAT Control Setpoint °F 100-180 135
18 Hydronic Heating ON-OFF ON-OFF OFF
19 First Stage Hydronic Heating SAT Setpoint °F 80-180 120
20 Second Stage Hydronic Heating SAT Setpoint °F 80-180 150
21 Hydronic Heating Reverse Actuated Valve ON-OFF ON-OFF OFF
22 Remote Control ON-OFF ON-OFF OFF
23 VAV Upper Cooling SAT °F 40-70 60
24 VAV Lower Cooling SAT °F 40-70 55
25 VAV SAT Reset Setpoint °F 40-85 72
26 VAV Occupied Setpoint ON-OFF ON-OFF OFF
27 VAV Occupied Heating Setpoint °F 40-85 68
28 Morning Warm-Up ON-OFF ON-OFF ON
29 Morning Warm-Up RAT °F 50-85 70
30 Duct Static Setpoint " H2O 0 – 5” 1.5”
31 Building Pressure Setpoint " H2O neg .25 to .25 .1”
32 Economizer ON-OFF ON-OFF ON
33 Economizer First Stage °F 40-65 55
34 Economizer Second Stage °F 40-65 50
35 Economizer Minimum Position Percent 0 to 100% 20
36 Outside Air Humidity Sensor ON-OFF ON-OFF OFF
37 Economizer Outside Air Enthalpy Setpoint BTUs Per Pound 10-50 27
38 Return Air Humidity Sensor ON-OFF ON-OFF OFF
39 Economizer OAT Enable °F 40-80 55
40 Demand Ventilation ON-OFF ON-OFF OFF
41 IAQ Sensor Range PPM 0-5000 2000
42 Demand Ventilation Setpoint PPM 0-5000 1000
43 Power Exhaust ON-OFF ON-OFF ON
44 Modulating Exhaust ON-OFF ON-OFF OFF
45 Exhaust VFD Installed ON-OFF ON-OFF OFF
46
Exhaust Damper Position for Exhaust Fan to
Turn On (Modulating Only)
% Of Damper Position 0-100 80%

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York MILLENIUM SIMPLICITY ELITE Series and is the answer not in the manual?

York MILLENIUM SIMPLICITY ELITE Series Specifications

General IconGeneral
BrandYork
ModelMILLENIUM SIMPLICITY ELITE Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals