351579-YTS-B-0608
Johnson Controls Unitary Products 9
Table 3: Simplicity
®
Control Inputs
Name Range Resolution Precision Description
Y1 18 - 30 VAC On - Off +/- .5 VAC Request for the first stage of Cooling (24 VAC sense) Tstat Screw Terminal
Y2 18 - 30 VAC On - Off +/- .5 VAC Request for the second stage of Cooling (24 VAC sense) Tstat Screw Terminal
Y3 18 - 30 VAC On - Off +/- .5 VAC Request for the third stage of Cooling (24 VAC sense) Tstat Screw Terminal
Y4 18 - 30 VAC On - Off +/- .5 VAC Request for the fourth stage of Cooling (24 VAC sense) Tstat Screw Terminal
W1 18 - 30 VAC On - Off +/- .5 VAC Request for the first Stage of Heating (24 VAC sense) Tstat Screw Terminal
W2 18 - 30 VAC On - Off +/- .5 VAC Request for the second Stage of Heating (24 VAC sense) Tstat Screw Terminal
W3 18 - 30 VAC On - Off +/- .5 VAC Request for the third Stage of Heating (24 VAC sense) Tstat Screw Terminal
G 18 - 30 VAC On - Off +/- .5 VAC Request for the Fan (24 VAC sense) Tstat Screw Terminal
R 18 - 30 VAC - -
These terminals are a ¼' Female Faston and a Thermostat Screw terminal
connected to the power supply of the board.
C Earth Ground - - These terminals are a ¼' Faston and a Thermostat Screw terminal.
OCC 18 - 30 VAC On - Off +/- .5 VAC Occupied input (24 VAC sense) Tstat Screw Terminal
SD 18 - 30 VAC - +/- .5 VAC Shut Down input Tstat Screw Terminal
Purge 18 - 30 VAC On - Off +/- .5 VAC Building Purge input (24 VAC sense) Tstat Screw Terminal
BAS Economizer 2 - 10 VDC Not Read by micro - Input that routes to the Economizer output Two Tstat Screw Terminals +&-
HPS1 18 - 30 VAC On - Off +/- .5 VAC High Pressure Switch for Circuit # 1 (24 VAC sense)
HPS2 18 - 30 VAC On - Off +/- .5 VAC High Pressure Switch for Circuit # 2 (24 VAC sense)
HPS3 18 - 30 VAC On - Off +/- .5 VAC High Pressure Switch for Circuit # 3 (24 VAC sense)
HPS4 18 - 30 VAC On - Off +/- .5 VAC High Pressure Switch for Circuit # 4 (24 VAC sense)
LPS1 18 - 30 VAC On - Off +/- .5 VAC Low Pressure Switch for Circuit # 1 (24 VAC sense)
LPS2 18 - 30 VAC On - Off +/- .5 VAC Low Pressure Switch for Circuit # 2 (24 VAC sense)
LPS3 18 - 30 VAC On - Off +/- .5 VAC Low Pressure Switch for Circuit # 3 (24 VAC sense)
LPS4 18 - 30 VAC On - Off +/- .5 VAC Low Pressure Switch for Circuit # 4 (24 VAC sense)
Limit Switch 1 18 - 30 VAC On - Off +/- .5 VAC High Limit Switch input (24 VAC sense) For Burner section 1
Limit Switch 2 18 - 30 VAC On - Off +/- .5 VAC High Limit Switch input (24 VAC sense) For Burner section 2
Limit Switch 3 18 - 30 VAC On - Off +/- .5 VAC High Limit Switch input (24 VAC sense) For Burner section 3
GV1 18 - 30 VAC On - Off +/- .5 VAC Gas Valve input (24 VAC sense) For Burner section 1
GV2 18 - 30 VAC On - Off +/- .5 VAC Gas Valve input (24 VAC sense) For Burner section 2
GV3 18 - 30 VAC On - Off +/- .5 VAC Gas Valve input (24 VAC sense) For Burner section 3
Test / Reset / Up ON - Off ON - Off - Test / Reset Button and Increment Data Input
Address / Down ON - Off ON - Off - Address Button and Decrement Data Input
Alarms / Advance Data ON - Off ON - Off - Alarm Button and Advance Data Input
Program ON - Off ON - Off - Program Button Input
Real Time Clock
24 hours, 365 Days
including Leap year
and Daylight
Savings Time
Seconds - Real Time Clock Chip
Water Coil Freeze Stat
(FSI)
18 - 30 VAC On - Off +/- .5 VAC Hot Water Freeze Stat (24 VAC sense) two ¼ Fastons
Supply Air Temp Sensor
(SAT)
-40° - +180° F .1° F
-40° - 180 °F
+/- 2 °F across
range
This is a 10KΩ type 3 Thermistor
Outside Air Temp Sensor
(OAT)
-40° - +180° F .1° F
-40° - 180 °F
+/- 2 °F across
range
This is a 10KΩ type 3 Thermistor
Space Temp Sensor
(ST)
32° - 100° F .1° F .5° F This is a 10KΩ type 3 Thermistor
Return Air Temp Sensor
(RAT)
-40° - +180° F .1° F
- 4 0 ° - 1 8 0 ° F
+/- 2 °F across
range
This is a 10KΩ type 3 Thermistor
Space Setpoint Offset
(SSA)
0 - 20 KΩ 1 KΩ + and - 250 Ω
3 position Mini Screw Terminal shared with Space Temp The common terminal
in the center is common for both the Space Temp and Setpoint Offset.
Building Pressure
Sensor
(BPS)
0 - 5 VDC-.25 - +.25
"WC
.001 "WC
.005 "WC
1% Across range
0 - 5 volt input
Duct Pressure Sensor
(DPS)
0 - 5 VDC0 - 5 "WC .01 "WC
. 0 5 " W C 1 %
across range
0 - 5 volt input
APS (APS) 18 - 30 VAC On - Off +/- .5 VAC Air Proving Switch (24 VAC sense)
Fan Overload (FOVR) 18 - 30 VAC On - Off +/- .5 VAC Fan Overload Switch (24 VAC sense)
CV / VAV Input 0 - 20 KΩ 1Ω + / - 5 Ω
Resistive Input 0 - 5.5K = CV 10K - 20K = VAV

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York MILLENIUM SIMPLICITY ELITE Series and is the answer not in the manual?

York MILLENIUM SIMPLICITY ELITE Series Specifications

General IconGeneral
BrandYork
ModelMILLENIUM SIMPLICITY ELITE Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals