11
YORK INTERNATIONAL
FORM 201.19-EG4
Temperatures and Flows
NOTES:
1. For leaving brine temperature below 40°F, contact your nearest YORK ofce for application requirements.
2. For leaving water temperature higher than 5.5°F, contact the nearest YORK ofce for application guidelines.
3. The evaporator is protected against freeze-up to -20°F with an electrical heater as standard.
ENGLISH UNITS
NOTES:
1. For leaving brine temperature below 5°C, contact your nearest YORK ofce for application requirements.
2. For leaving water temperature higher than 13°C, contact the nearest YORK ofce for application guidelines.
3. The evaporator is protected against freeze-up to -28.8°C with an electrical heater as standard.
MODEL
LEAVING WATER
COOLER FLOW
AIR ON
NUMBER
TEMPERATURE (°C) (L/S)
3
CONDENSER (°C)
YCAS
MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
0098 4.4 12.8 8.9 25.4 -17.7 50
0118 4.4 12.8 8.9 25.4 -17.7 50
0128 4.4 12.8 11.3 48.5 -17.7 50
0138 4.4 12.8 8.9 25.4 -17.7 50
0148 4.4 12.8 11.3 48.5 -17.7 50
0158 4.4 12.8 11.3 48.5 -17.7 50
0178 4.4 12.8 11.3 48.5 -17.7 50
0198 4.4 12.8 11.3 48.5 -17.7 50
0208 4.4 12.8 11.3 48.5 -17.7 50
0218 4.4 12.8 20.0 67.6 -17.7 50
0248 4.4 12.8 20.0 67.6 -17.7 50
0268 4.4 12.8 20.0 67.6 -17.7 50
0288 4.4 12.8 26.0 76.0 -17.7 50
0308 4.4 12.8 26.0 76.0 -17.7 50
0328 4.4 12.8 26.0 76.0 -17.7 50
0358 4.4 12.8 34.0 101.0 -17.7 50
0398 4.4 12.8 34.0 101.0 -17.7 50
0418 4.4 12.8 34.0 101.0 -17.7 50
SI UNITS
MODEL
LEAVING WATER
COOLER FLOW
AIR ON
NUMBER
TEMPERATURE (°F) (GPM)
3
CONDENSER (°F)
YCAS
MIN.
1
MAX
.2
MIN. MAX. MIN. MAX
0098 40 55 141 403 0 125
0118 40 55 141 403 0 125
0128 40 55 180 768 0 125
0138 40 55 141 403 0 125
0148 40 55 180 768 0 125
0158 40 55 180 768 0 125
0178 40 55 180 768 0 125
0198 40 55 180 768 0 125
0208 40 55 180 768 0 125
0218 40 50 318 1072 0 125
0248 40 50 318 1072 0 125
0268 40 50 318 1072 0 125
0288 40 50 415 1205 0 125
0308 40 50 415 1205 0 125
0328 40 50 415 1205 0 125
0358 40 50 530 1601 0 125
0398 40 50 530 1601 0 125
0418 40 50 530 1601 0 125