254595-YTG-C-0308
28 Johnson Controls Unitary Products
FIGURE 7 - DISCONNECT/BLOWER ACCESS LOCATION
Disconnect Switch Location
and Motor Access Panel for
Unit with “Belt-Drive” Option
Control Box Access
A,B
Wiring Entry
(See Detail “B”)
Mounting Bracket for
Disconnect Switch
(Field Supplied)
Field-Supplied Disconnect
Switch Location
Blower Motor Access
Filter Access
Dot Plugs
TABLE 28: UTILITIES ENTRY
HOLE OPENING SIZE (DIA.) USED FOR
A
7/8” KO
1
Control Wiring
2
Side
Bottom
B
2” KO
1
Power Wiring
Side
Bottom
C
1-5/8” KO Gas Piping (Front)
D
1-1/2” KO
Gas Piping (Bottom)
1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2” knockout ring.
TABLE 29: MINIMUM CLEARANCES
LOCATION
CLEARANCE
Front
24” (Cooling/Electric Heat)
32” (Gas Heat)
Rear
12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)
Left Side (Filter Access)
24” (Less Economizer)
36” (With Economizer)
Right Side (Cond. Coil)
24”
Below Unit
1
0”
Above Unit
2
72” (For
Condenser Air Discharge)
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York Sunline 2000 BQ 036 and is the answer not in the manual?

York Sunline 2000 BQ 036 Specifications

General IconGeneral
BrandYork
ModelSunline 2000 BQ 036
CategoryHeat Pump
LanguageEnglish

Related product manuals