JOHNSON CONTROLS
SECTION 7 – UNIT CONTROLS
FORM 150.67-NM1
ISSUE DATE: 4/28/2017
7
Option 19 – Pump Control
Pump Control is utilized to operate the optional on-
board pump kit or to control an external pump through
dry contacts 23 and 24. To use this option, the follow-
ing selection should be made in the Service Mode:
Y O R K H Y D R O
K I T P U M P S = 1
When YORK HYDRO KIT PUMPS = 1, the controls
will be closed to run the pumps whenever any one of
the following conditions are true:
• Low Leaving Chilled Liquid Fault
• Any compressor is running
• Daily Schedule is ON and Remote Stop is closed.
Even if one of the above conditions
are true, the pump will not run if the
chiller has been powered up for less
than 30 seconds; or if the pump has
run in the last 30 seconds to prevent
pump overheating.
E X T E R N A L
E V A P P U M P
EXTERNAL EVAP PUMP should be selected if an ex-
ternal pump is being controlled with the chiller pump
contacts. The operation will be the same as YORK
HDRO KIT PUMPS = 1
The following option should not be selected.
Y O R K H Y D R O
K I T P U M P S = 2
Option 20 – Pump Selection
The displays for this PUMP SELECTION option
should only appear if “YORK HYDRO KIT PUMPS =
2” are selected under Option 19. Presently, this option
should not be used.
CLOCK
The CLOCK display shows the current day, time, and
date. Pressing the CLOCK key will show the current
day, time, and date.
It is important that the date and time be correct, other-
wise the daily schedule will not function as desired if
programmed. In addition, for ease of troubleshooting
via the History printouts, the day, time, and date should
be correct.
To change the day, time, and date press the CLOCK
key. The display will show something similar to the
following:
T O D A Y I S F R I 0 8 : 5 1 A M
2 5 J A N 0 2
The line under the F is the cursor. If the day is correct,
press the ENTER/ADV key. The cursor will move un-
der the 0 in 08 hours. If the day is incorrect, press the
↑(UP)or↓(DOWN)arrowkeysuntilthedesiredday
is displayed and then press the ENTER/ADV key at
which time the day will be accepted and the cursor will
move under the first digit of the “2 digit hour”. In a
similar manner, the hour, minute, meridian, month, day,
and year may be programmed, whenever the cursor is
underthefirst letter/numeral oftheitem. Press the↑
(UP)or↓(DOWN)arrowkeysuntilthedesiredhour,
minute, meridian; day, month, and year are displayed.
Pressing the ENTER/ADV key will save the valve and
move the cursor on to the next programmable variable.
Jumper J11 on the microboard must
be set to the “CLKON” position to
turn on the clock. If this is not done,
the clock will not function.

Table of Contents

Other manuals for York YCAL0022

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YCAL0022 and is the answer not in the manual?

York YCAL0022 Specifications

General IconGeneral
BrandYork
ModelYCAL0022
CategoryChiller
LanguageEnglish

Related product manuals