SECTION 5 – TECHNICAL DATA
TABLE 11 - ELECTRICAL DATA WITHOUT PUMPS
CHILLER
MODEL
VOLTAGE
CODE
MIN CKT.
AMPS
MIN N/F
DISC SW
MIN DUAL
ELEM
FUSE AND
MIN CB
MAX DUAL
ELEM
FUSE
MAX CB
41
208 172 250 200 200
230 171 250 200 200
380 119 150 125 125
460 92 150 100 100
575 66 100 70 70
48
208 248 400 250 250
230 248 400 250 250
380 137 200 150 150
460 114 150 125 125
575 96 150 110 110
58
208 276 400 300 300
230 275 400 300 300
380 149 200 175 175
460 130 200 150 150
575 103 150 110 110
65
208 306 400 350 350
230 305 400 350 350
380 170 250 200 200
460 150 200 175 175
575 112 150 125 125
70
208 334 400 350 350
230 333 400 350 350
380 191 250 225 225
460 169 200 175 175
575 120 150 125 125
80
208 363 600 400 400
230 363 600 400 400
380 201 250 225 225
460 177 250 200 200
575 134 200 150 150
81
208 363 400 400 400
230 363 400 400 400
380 201 250 225 225
460 177 250 200 200
575 134 200 150 150
82
208 363 600 400 400
230 363 600 400 400
380 201 250 225 225
460 177 250 200 200
575 134 200 150 150
89
208 391 600 450 450
230 390 600 450 450
380 211 250 250 250
460 184 250 200 200
575 146 200 150 150

Table of Contents

Other manuals for York YLAA0170

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YLAA0170 and is the answer not in the manual?

York YLAA0170 Specifications

General IconGeneral
BrandYork
ModelYLAA0170
CategoryChiller
LanguageEnglish

Related product manuals