Section 3 - Maintenance
Maintenance inspections for YORK YMC
2
chillers
To avoid serious operating difficulty, follow a regular
inspection procedure. Use the following list of inspec-
tions and procedures as a guide.
Daily
Check the OptiView™ Control Center display.
Log the date, time, run hours, and number of
starts.
Use the daily log in the YMC
2
centrifugal liquid
chiller log sheet, Form 160.78-MR1, to log all of
the unit operating data that is outlined in the log.
Use this data for the following comparisons:
Compare the entering and leaving condenser
water temperatures with the job design con-
ditions. Check the condenser water tempera-
tures on the System screen.
Compare the entering and leaving chilled
liquid temperatures and evaporator pressure
with the job design conditions. Check the
chilled liquid temperatures on the System
screen.
Check the condenser saturation temperature
on the System screen. The condenser satu-
ration temperature is based on the condens-
er pressure that is sensed by the condenser
transducer.
Check the compressor discharge temperature
on the System screen. During normal opera-
tion, the discharge temperature does not ex-
ceed 220°F (104°C).
Check the compressor motor current on the
Compressor screen.
Weekly
Check the refrigerant charge. See Checking the
refrigerant charge during unit shutdown.
Check for any signs of dirty or fouled condenser
tubes. The temperature dierence between the
water leaving the condenser and the saturated
condensing temperature must not exceed the dif-
ference recorded for a new unit by more than 4°F
(2.2°C).
Monthly (or more often as required)
Log and compare the VSD input voltage current
for balanced values in the readings.
Verify that the unit setpoints have not been
changed. Check the setpoints in the Security Log
screen.
Verify that the evaporator and condenser water
ows are within rated limits.
Check the operation of the motor starter. Monitor
at unit start-up for any abnormalities.
Annually (more often if necessary)
For the evaporator and condenser, complete the
following inspections:
Inspect and clean the water strainers.
Inspect and clean the tubes as required.
Inspect the end sheet.
For the compressor drive motor, measure the mo-
tor winding insulation resistance (megohm test-
ing).
Check and tighten all of the electrical components
as necessary
Clean and backush the VSD heat exchanger.
Replace the VSD coolant.
Perform refrigerant analysis.
For all HYP model VSDs, conduct a Smart Sensor
annual test.
Review the operating data for trends that indicate
increasing vibration or power consumption.