271457-YTG-B-0908
20 Johnson Controls Unitary Products
CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the
total electric power input during the same period.
HEATING CAPACITY - YZB04211With Variable Speed Furnaces
VARIABLE
SPEED
FURNACE
COIL
1
MODEL
ARI HEATING
2
47°F17°FHSPF
MBH COP KW MBH COP KW STD
1 PH 13 SEER HP WITH VARIABLE SPEED FURNACES
PV8*C16 FC/MC/PC48C 42.03.663.3628.42.543.288.00
PV8*C20 FC/MC/PC48C 42.03.663.3628.42.543.288.00
P(C,V)9*C16 FC/MC/PC48C 42.03.743.2928.02.583.188.60
P(C,V)9*C20 FC/MC/PC48C 42.03.763.2728.02.603.168.60
P(C,V)9*D20 FC/MC/PC48D 42.03.743.2928.02.583.188.60
PV8*C20 HC48 42.03.663.3628.42.543.288.00
P(C,V)9*C20 HC48 42.03.663.3628.42.543.288.00
PV8*C20 HD48 42.03.663.3628.42.543.288.00
P(C,V)9*C20 HD48 42.03.663.3628.42.543.288.00
Y*(8,L)C*C16 FC/MC/PC48C 41.5 3.80 3.20 28.0 2.62 3.13 8.10
Y*(8,L)C*C20 FC/MC/PC48C 41.5 3.82 3.18 27.8 2.64 3.09 8.20
Y*9C*C16 FC/MC/PC48C 41.5 3.78 3.22 28.0 2.60 3.16 8.10
Y*9C*C20 FC/MC/PC48C 42.0 3.76 3.27 28.2 2.60 3.18 8.10
Y*9C*D20 FC/MC/PC48D 41.5 3.78 3.22 28.0 2.62 3.13 8.10
Y*(8,L)C*B12 HD48 41.0 3.32 3.62 27.2 2.30 3.47 7.80
Y*(8,L)C*C16 HD48 41.0 3.46 3.47 27.0 2.36 3.35 7.90
Y*(8,L)C*C20 HD48 40.5 3.48 3.41 26.8 2.36 3.33 7.90
Y*9C*B12 HD48 40.0 3.16 3.71 27.0 2.24 3.53 7.80
Y*9C*C16 HD48 41.0 3.40 3.53 27.6 2.32 3.49 7.90
Y*9C*C20 HD48 41.0 3.38 3.56 27.6 2.32 3.49 7.90
Y*9C*D20 HD48 41.0 3.44 3.49 27.0 2.34 3.38 7.90
Y*(8,L)C*C16 UC48C 42.0 3.90 3.16 28.0 2.68 3.06 8.20
Y*(8,L)C*C20 UC48C 42.0 3.94 3.12 28.0 2.70 3.04 8.20
Y*9C*C16 UC48C 42.0 3.88 3.17 28.2 2.66 3.11 8.20
Y*9C*C20 UC48C 42.0 3.86 3.19 28.2 2.64 3.13 8.20
Y*9C*D20 UC48D 42.0 3.90 3.16 28.0 2.66 3.09 8.20
G*9V*C16 FC/MC/PC48C 41.5 3.78 3.22 28.0 2.60 3.16 8.10
G*9V*C20 FC/MC/PC48C 42.0 3.76 3.27 28.2 2.60 3.18 8.10
G*9V*D20 FC/MC/PC48D 41.5 3.78 3.22 28.0 2.62 3.13 8.10
G*9V*B12 HD48 40.0 3.16 3.71 27.0 2.24 3.53 7.80
G*9V*C16 HD48 41.0 3.40 3.53 27.6 2.32 3.49 7.90
G*9V*C20 HD48 41.0 3.38 3.56 27.6 2.32 3.49 7.90
G*9V*D20 HD48 41.0 3.44 3.49 27.0 2.34 3.38 7.90
G*9V*C16 UC48C 42.0 3.88 3.17 28.2 2.66 3.11 8.20
G*9V*C20 UC48C 42.0 3.86 3.19 28.2 2.64 3.13 8.20
G*9V*D20 UC48D 42.0 3.90 3.16 28.0 2.66 3.09 8.20
1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no
supplemental electric heat operation.