Johnson Controls Unitary Products 7
COOLING CAPACITY - YZB02411With Variable Speed Furnaces
VARIABLE SPEED
FURNACE MODEL
COIL
MODEL
1
W
COOLING
RATED
CFM
NET MBH
SEER EER
TOTAL SENS.
1 PH 13 SEER HP WITH VARIABLE SPEED FURNACES
2
PV8*A12 FC/MC/PC24A 14 750 23.0 16.1 13.50 11.00
PV9*A12 FC/MC/PC24A 14 800 23.0 16.1 14.00 11.50
PV8*A12 FC/MC/PC30A 14 750 23.0 16.1 13.50 11.00
PV9*A12 FC/MC/PC30A 14 800 23.0 16.1 14.00 11.50
Y*(8,L)C*A12 FC/MC/PC24A 14 805 23.2 17.7 14.60 12.20
Y*(8,L)C*B12 FC/MC/PC24B 17 815 23.4 17.7 14.90 12.30
Y*9C*B12 FC/MC/PC24B 17 790 23.2 17.7 14.60 12.20
Y*(8,L)C*A12 FC/MC/PC30A 14 805 23.2 17.7 14.60 12.20
Y*(8,L)C*B12 FC/MC/PC30B 17 815 23.4 17.7 14.90 12.30
Y*9C*B12 FC/MC/PC30B 17 790 23.2 17.7 14.60 12.20
Y*(8,L)C*A12 FC/MC/PC32A 14 775 23.4 17.5 14.50 12.10
Y*(8,L)C*A12 HC30 14 775 23.2 17.3 14.30 12.00
Y*(8,L)C*A12 HD24 14 805 23.6 17.8 14.90 12.40
Y*(8,L)C*B12 HD24 17 815 23.8 17.9 15.10 12.50
Y*9C*B12 HD24 17 790 23.6 17.8 14.90 12.40
Y*(8,L)C*A12 UC24A 14 805 23.6 17.8 14.80 12.30
Y*(8,L)C*B12 UC24B 17 815 23.6 17.8 15.10 12.50
Y*9C*B12 UC24B 17 790 23.6 17.8 14.80 12.30
Y*(8,L)C*A12 UC30A 14 805 23.6 17.8 14.80 12.30
Y*(8,L)C*B12 UC30B 17 815 23.6 17.8 15.10 12.50
Y*9C*B12 UC30B 17 790 23.6 17.8 14.80 12.30
G*9V*A12 FC/MC/PC24A 14 800 23.2 17.5 14.20 11.90
G*9V*B12 FC/MC/PC24B 17 790 23.2 17.7 14.60 12.20
G*9V*A12 FC/MC/PC30A 14 800 23.2 17.5 14.20 11.90
G*9V*B12 FC/MC/PC30B 17 790 23.2 17.7 14.60 12.20
G*9V*A12 FC/MC/PC32A 14 800 23.4 17.6 14.10 11.80
G*9V*A12 HC30 14 800 23.4 17.5 14.40 12.00
G*9V*A12 HD24 14 800 23.6 17.7 14.60 12.10
G*9V*B12 HD24 17 790 23.6 17.8 14.90 12.40
G*9V*A12 UC24A 14 800 23.4 17.6 14.40 12.10
G*9V*B12 UC24B 17 790 23.6 17.8 14.80 12.30
G*9V*A12 UC30A 14 800 23.4 17.6 14.40 12.10
G*9V*B12 UC30B 17 790 23.6 17.8 14.80 12.30
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Variable speed furnaces have B.O.D (Blower on Delay) standard.