12.4.5 Zapi menu “HARDWARE SETTINGS” functions list
To enter this Zapi hidden menu a special procedure is required. Ask this procedure
directly to a Zapi technician.
1) MAXIMUM CURRENT
MAXIMUM CURENT sets the limit for the current in the controller.
2) CAN BUS
ABSENT or PRESENT. This setting specifies whether the eps-ac0 is CAN Bus
connected or not. When CAN BUS is ABSENT, the CAN BUS KO alarm is
inhibited together with any starting sequence used to synchronize via CAN Bus
the eps-ac0 with the other controllers.
3) SET HI RESOL AD
When it is set to Level 1, enables an analog to digital conversion with high
resolution applied to the command pot CPOC1. Level 0 means the high
resolution AD conversion is inhibited. Level 2 is not used.