AEMZP0BA - EPS-AC0 - User Manual Page - 77/95
- LEVEL 1-9 Zapi reserved.
- LEVEL 10: Enables the NO LOAD CURRENT test (see 12.4.2.10). Roll
from level 10 to level 15 and save the new setting to exit this
testing condition.
- LEVEL 11: Disables the alarms FB SENS LOCKED, MOTOR LOCKED
and POSITION ERROR (the latest only for FB ENC &
Toggle Switches configuration) till a new DEBUG OUTPUT
hand setting.
- LEVEL 12: The SET POINT POT of the Tester menu is connected at the
high resolution AD input (it is in the range 0 to 5Vdc when
the command potentiometer (CPOC1) is close to ZERO SP
POT).
- LEVEL 13: Reading SET POINT POT in the tester menu is connected to
the 2nd wiper of the twin (command) pot (CPOC2 on
CNA#8).
- LEVEL 14: Disables the alarms FB POT LOCKED, MOTOR LOCKED
and POSITION ERROR (the latest only for FB ENC &
TOGGLE SWs configuration). It switches automatically to the
default Level 15 recycling the key.
- LEVEL 15: Default value (no special functions activated).