19
Be sure to read the installation and
operating manual before installing.
This allows you to protect yourself
and prevent damage. Check the
contents of the package before ins-
tallation to be complete.
Technical data flow sensor type IUF
Nominal ow q
p
m³/h 0.6 1.5 2.5 3.5 6 10
Maximum ow q
s
m³/h 1.2 3 5 7 12 20
Minimum ow q
i
l/h
6
12
15
30
25
50
35
70
60
120
100
200
Pressure loss at q
p
bar ≤0.25
Temperature range (*) °C 0 ≤ Ɵ q ≤ 105 / 0 ≤ Ɵ q ≤ 130
Minimum pressure
(to avoid cavitation)
bar
1 bar at q
p
and
80 °C medium temperature
Meassurement accuracy class (*) 2 (optional 3)
Nominal pressure
■
Body with thread connection
■
Body with ange/DN
PS/PN
PS/PN
16/16
25/25
IP protection class 68
Installation position in any position
Installation point return pipe, optionally supply pipe
Cable length up to calculator 1,2
Installation place temperature
sensors
m M10 x 1
Heat carrier (Medium) Water
(*) optionally
Purchased parts package
■
zelsius
®
C5 ow sensor with calculator
■
O-Ring respectively gasket
■
Seal material
■
Wall holder with mounting accessories
■
Installation and operating manual
ItalianoEspañol