Planning the electrical installation 45
Protecting the motor and motor cable in short circuits
The drive protects the motor cable and motor in a short-circuit situation when:
the motor cable is sized correctly
the motor cable type complies with the motor cable selection guidelines by ABB
the cable length does not exceed the allowed maximum length specified for the
drive
the setting of parameter 99.10 Motor nominal power is equal to the value on the
motor rating plate.
The electronic power output short-circuit protection circuitry meets the
requirements of IEC 60364-4-41 2005/AMD1, Clause 411.