EasyManuals Logo

ABB ACS800-07 User Manual

ABB ACS800-07
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
Filters (E)
21
ACS800-U7: Not available.
ACS800-07 frames n×R8i: Not available with the special construction options
+C121, +C129 or +C134.
ACS800-17 and ACS800-37: Not available for frame R6 or with C121 or C129.
More information: ACS800 Sine Filters User’s Manual (3AFE68389178 [English]).
Common mode filter (E208)
The common mode filter contains ferrite rings mounted around the drive DC
busbars. The filter protects the motor bearings by reducing the bearing currents.
ACS800-07 and ACS800-U7: Not available for frames R5 and R6 except 0135-3,
0165-3, 0205-3, 0165-5, 0205-5, 0255-5, 0145-7, 0175-7 and 0205-7.
ACS800-17 and ACS800-37: Not available for frame R6.
Standard for
ACS800-07 frames n×R8i and ACS800-U7 frame R8
ACS800-17/37 frames R7i, R8i and n×R8i.
More information on when the option is required: See section Checking the
compatibility of the motor and the drive in the drive hardware manual.

Table of Contents