CMS-700 SYSTEM CIRCUIT MONITORING SYSTEM (CMS)
37
WEB UI - Settings Menu
Settings Menu - Communication / SNMP
The SNMP service is disabled on the device by default. In order to activate it, it is necessary to
open the following panel:
Version 1/2c: To enable versions 1 and 2c mark the v.1/2c checkbox, enter port number and password
for the protocol. The port number must be 161 or greater than 1024. The SNMP service is working on
UDP port so there is no port collision with the Modbus or web service which are working on TCP ports.
The password must have at least 5 signs. In versions 1 and 2c authentication is only by the password
which is not encrypted.