Communication
105
Table 12. PROFIdrive Response header
Drive
Object ID
To be set to 0 or 1. 0 255 Byte
No. of
Parameters
Number of parameters that are present in
the request.
1…37 Byte
Attribute Type of object being accessed.
Note: “Description” and “Text” are not
supported.
Value (10h)
Description (20h)
Text (30h)
Byte
No. of
Elements
Number of array elements accessed or
length of string accessed. Set to 0 if non-
array parameters are used.
0, 1 234 Byte
Parameter
Index
Address of the parameter that is being
accessed. “0” is allowed by FPBA-01.
1 65535 Word
Subindex Addresses the first array element of the
parameter or the beginning of a string
access or the text array, or the description
element that is being accessed.
0 65535 Word
Format* See Table 13. See Table 13 Byte
Number of
Values*
Number of values following. 0 234 Byte
Values* The values of the request. In case of odd
number of bytes, a zero byte is appended
to ensure the word structure of the
telegram.
See
Format
field
*Only if Request ID is 02h (Change Parameter). The Format, Number of Values and
Values fields are repeated for other parameters.
Field(s) Description Range
Response
Reference
Mirrored from the request. 1 255
Response
ID
Response from the slave. In case any
requested services fail, a “not
acknowledged” (NAK) response will be
indicated.
Request Param OK (01h)
Request Param NAK (81h)
Change Param OK (02h)
Change Param NAK (82h)

Table of Contents

Other manuals for ABB FPBA-01

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB FPBA-01 and is the answer not in the manual?

ABB FPBA-01 Specifications

General IconGeneral
BrandABB
ModelFPBA-01
CategoryAdapter
LanguageEnglish

Related product manuals