Drive configuration
42
Table 1. FPBA-01 configuration parameters – Group A
Note: Set also the extended Parameter Data (see SAP 61 in the
chapter Communication) to ensure proper operation of the
FPBA-01 with the drive.
1 FBA TYPE
This parameter shows the fieldbus adapter type as detected by
the drive. The value cannot be adjusted by the user.
If this parameter is undefined, the communication between the
drive and the module has not been established.
Par.
no.
Parameter name Alternative settings Default
setting
1 FBA TYPE (Read-only) PROFIBUS DP
2 NODE ADDRESS 0 to 126 3
3 BAUD RATE* (12000) 12 Mbit/s; (6000) 6 Mbit/s;
(3000) 3Mbit/s; (1500) 1.5 Mbit/s;
(500) 500 kbit/s; (187) 187.5 kbit/s;
(93) 93.75 kbit/s; (45) 45.45 kbit/s;
(19) 19.2 kbit/s; (9) 9.6 kbit/s
1500
4 TELEGRAM TYPE* (1) PPO 1; (2) PPO 2; (3) PPO 3;
(4) PPO 4; (5) PPO 5; (6) PPO 6;
(7) ST1; (8) ST2**
(Read-only)
(1) PPO 1
5PROFILE (0) PROFIdrive; (1) ABB Drives;
(2) Transparent 16;
(3) Transparent 32**;
(4) PROFIdrive positioning mode**
(1) ABB Drives
6 T16 SCALE 1 to 65535 100
*The value is automatically updated (Read-only).
**Only supported with an ACSM1/ACS850 drive.