Drive configuration
44
More information on the communication profiles can be found in
the chapter Communication profiles.
6 T16 SCALE
Reference multiplier/actual value divisor for the FPBA-01. The
parameter is effective only when the Transparent 16 profile is
selected AND the drive is using the DCU communication profile.
With an ACS350, the speed reference from the PLC is multiplied
by the value of this parameter. For example, with the default
setting of 100, a reference of 1,000 is forwarded to the drive as
100,000. According to the DCU profile, this value is interpreted as
a reference of 100 rpm.
With an ACSM1, setting this parameter to 65535 will provide the
practically exact approximation of 1 ≈ 1 rpm.