MOUNTING AND OPERATION MANUAL INDOOR AIR SWITCH-DISCONNECTOR, NAL/NALF/VR
21.1 Replacement of contact knives
1. Disconnect the switch-disconnector. When
A-mechanism is fitted, the opening spring
must NOT be charged.
2. The draw bar is detached from the crank arm
of the operating shaft, see Fig. 116.
3. The contact screw is detached and the
contact knives are removed, see Fig.117.
4. Replacement contact knifes are lubricated
with ISOFLEX TOPAS NCA 52 and mounted to
the contact block with the contact screw.
5. Check that the contact knives can move
easily and operate correctly over the
opposite contacts.
6. Before the drawbar is connected to the crank
arm of the operating shaft, see Fig. 116
ensure that the auxiliary knives run easily in
the individual arc extinguishing chambers,
and that the main knives make proper
contact.
7. Put contact grease on the main contacts
before the first test operation. The contact
position is adjusted by the eccentric bolt on
the operating shaft. It can also be adjusted
by adjusting the support insulator.
116 Detached draw bar
117 Detached contact screw
21.0 Replacement of parts in NAL/VR
36 kV
b
a
_
WARNING!
These operations shall be carried out by
authorised ABB service only!

Table of Contents

Other manuals for ABB NAL Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB NAL Series and is the answer not in the manual?

ABB NAL Series Specifications

General IconGeneral
BrandABB
ModelNAL Series
CategorySwitch
LanguageEnglish

Related product manuals