Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 57 Chapter 7
7.3 List of available parameters
A list of the available parameters for PSE18...PSE370 is visible in table 7.1.
Table 7.1
Description Display
symbol
Setting range Default
value
Access
from
Parameter
transfer with
External Keypad
Actual setting
HMI
Fieldbus
Rated Current of motor I
e
Individual
See tables in
chapter 3.7.3
PSE Softstarter
types. Setting
range is 30-100
percent of I
e
Individual W W
Start Ramp time
1...30 s 10 s W W T
Stop Ramp time
OFF, 1...30 s OFF W W T
Initial/End Voltage
30...70 % 30 % W W T
Current limit
1.5 x 7
I
e
4.0 x I
e
W W T
Torque Control during start ramp
OFF/On OFF W W T
Torque Control during stop ramp
OFF/On On W W T
Kick Start
OFF, 30...70 % OFF W W T
Electronic Motor Overload Protection
(EOL)
T
Tripping Class (EOL)
10 A, 10, 20,
30
10 W W T
Type of operation (EOL)
HAnd/Auto