GEN <254> Function type FUN INFORMATION
Read value of single entry <244>
Information number INF
OBJECT
<0>
Return information
identifier
RII
{1, 0, 0}
Number of generic data
sets
NGD {NO, COUNT, CONT}
43 H Generic identification
number
Group <41H .. 45H>
01 H Entry <1 .. 255>
Current value <1> Kind of description
KOD
DATA STRUCTURE
<23>
14
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD
<9> DOUBLE-POINT INFORMATION
1
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD 1
0 0 0 0 0 0 <0 .. 3>
GID 1
<14>
BINARY TIME
7
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD 2
Time stamp (CP56Time2a)
GID 2
4.5.4 Entries for double-point indications
GUID-F19F8A2D-F20A-4393-AEB3-66F5D3292526 v2
Table 25: Directory entry for GIN 0x4600 (header)
COD Data type Length Number Value / Significance
<10> Description <1> os8ascii 24 1 Double-point Indications
<1>Current value <3> UI 1 1 Number of DPI defined in this group.
Table 26: Directory entry for GIN 0x46 (xx)
COD Data type Length Number Value / Significance
<10> Description <1> os8ascii 20 1 Event text defined by user
<1> Current value <23> data
structure
14 1 (Includes the following two
definitions)
<9> Double
Point
INFORMATIO
N WITH
TRANSIENT
AND ERROR
1 1 TRANSIENT (0) /OFF (1) / ON (2) /
ERROR (3)
<14> binary
time
7 1 Time stamp (CP56Time2a)
The following table gives an example of the ASDU 10 Generic Data that is transferred
spontaneously for a double-point indication.
1MRK 511 451-UEN B Section 4
IEC60870-5-103
Distributed busbar protection REB500 23
Communication protocol manual IEC60870-5-103