Auto reclose control
The auto reclose control initiated by above described initiation logic follows
following schematic:
Figure
O
initiation logic during the set reclaim time t
the previous O
not conside
The auto reclose cycle could get interrupted respective aborted by the signal O
blocked and result in a final trip:
Figure
Protection and Control Function
Auto reclose control
The auto reclose control initiated by above described initiation logic follows
following schematic:
Figure
O
I
initiation logic during the set reclaim time t
the previous O
not conside
The auto reclose cycle could get interrupted respective aborted by the signal O
blocked and result in a final trip:
Figure
Protection and Control Function
Auto reclose control
The auto reclose control initiated by above described initiation logic follows
following schematic:
Figure
5
I
cycle 2 … 4 are initiated with a protection trip signal according the selected
initiation logic during the set reclaim time t
the previous O
not conside
The auto reclose cycle could get interrupted respective aborted by the signal O
blocked and result in a final trip:
Figure
6
Protection and Control Function
Auto reclose control
The auto reclose control initiated by above described initiation logic follows
following schematic:
5
:
Auto reclose control
cycle 2 … 4 are initiated with a protection trip signal according the selected
initiation logic during the set reclaim time t
the previous O
not conside
The auto reclose cycle could get interrupted respective aborted by the signal O
blocked and result in a final trip:
6
:
Auto reclose control
Protection and Control Function
Auto reclose control
The auto reclose control initiated by above described initiation logic follows
following schematic:
Auto reclose control
cycle 2 … 4 are initiated with a protection trip signal according the selected
initiation logic during the set reclaim time t
the previous O
not conside
red.
The auto reclose cycle could get interrupted respective aborted by the signal O
blocked and result in a final trip:
Auto reclose control
Protection and Control Function
In case if no binary inputs are configured for indicating circuit
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
Auto reclose control
The auto reclose control initiated by above described initiation logic follows
following schematic:
Auto reclose control
cycle 24 are initiated with a protection trip signal according the selected
initiation logic during the set reclaim time t
the previous O
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
red.
The auto reclose cycle could get interrupted respective aborted by the signal O
blocked and result in a final trip:
Auto reclose control
If the CB gets closed manually, the auto reclose function is
blocked for the time t
In case i
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
breaker position, the setting
0” (Auto Reclose not in use) to avoid any mal
Auto reclose control
The auto reclose control initiated by above described initiation logic follows
following schematic:
Auto reclose control
cycle 2 … 4 are initiated with a protection trip signal according the selected
initiation logic during the set reclaim time t
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
blocked and result in a final trip:
Auto reclose control
If the CB gets closed manually, the auto reclose function is
blocked for the time t
In case i
breaker position, the setting
0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
Auto reclose control
The auto reclose control initiated by above described initiation logic follows
following schematic:
Auto reclose control
cycle 2 … 4 are initiated with a protection trip signal according the selected
initiation logic during the set reclaim time t
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
blocked and result in a final trip:
Auto reclose control
If the CB gets closed manually, the auto reclose function is
blocked for the time t
In case i
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
The auto reclose control initiated by above described initiation logic follows
Auto reclose control
cycle 2 … 4 are initiated with a protection trip signal according the selected
initiation logic during the set reclaim time t
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
blocked and result in a final trip:
Auto reclose control
If the CB gets closed manually, the auto reclose function is
blocked for the time t
In case i
f no binary inputs are configured for indicating circuit
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
The auto reclose control initiated by above described initiation logic follows
Auto reclose control
cycle 2 … 4 are initiated with a protection trip signal according the selected
initiation logic during the set reclaim time t
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
blocked and result in a final trip:
Auto reclose control
If the CB gets closed manually, the auto reclose function is
blocked for the time t
f no binary inputs are configured for indicating circuit
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
The auto reclose control initiated by above described initiation logic follows
Auto reclose control
cycle 2 … 4 are initiated with a protection trip signal according the selected
initiation logic during the set reclaim time t
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
blocked and result in a final trip:
Auto reclose control
If the CB gets closed manually, the auto reclose function is
blocked for the time t
f no binary inputs are configured for indicating circuit
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
initiation logic during the set reclaim time t
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
blocked and result in a final trip:
If the CB gets closed manually, the auto reclose function is
blocked for the time t
f no binary inputs are configured for indicating circuit
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
initiation logic during the set reclaim time t
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
If the CB gets closed manually, the auto reclose function is
blocked for the time t
b
.
f no binary inputs are configured for indicating circuit
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
initiation logic during the set reclaim time t
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
If the CB gets closed manually, the auto reclose function is
.
f no binary inputs are configured for indicating circuit
breaker position, the setting
“0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
breaker position, the setting
O
“0” (Auto Reclose not in use) to avoid any mal
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
initiation logic during the set reclaim time t
r
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
If the CB gets closed manually, the auto reclose function is
f no binary inputs are configured for indicating circuit
breaker position, the setting
O
“0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
O
“0” (Auto Reclose not in use) to avoid any mal
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
r
. which is started by close command of
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
If the CB gets closed manually, the auto reclose function is
f no binary inputs are configured for indicating circuit
O
I
“0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
I
cycle
“0” (Auto Reclose not in use) to avoid any mal
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
. which is started by close command of
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
If the CB gets closed manually, the auto reclose function is
f no binary inputs are configured for indicating circuit
I
cycle
“0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
cycle
“0” (Auto Reclose not in use) to avoid any mal
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
. which is started by close command of
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
If the CB gets closed manually, the auto reclose function is
f no binary inputs are configured for indicating circuit
cycle
“0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
cycle
will automatically sets to
“0” (Auto Reclose not in use) to avoid any mal
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
. which is started by close command of
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
If the CB gets closed manually, the auto reclose function is
f no binary inputs are configured for indicating circuit
cycle
will automatically sets to
“0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
will automatically sets to
“0” (Auto Reclose not in use) to avoid any mal
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
. which is started by close command of
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
If the CB gets closed manually, the auto reclose function is
f no binary inputs are configured for indicating circuit
will automatically sets to
“0” (Auto Reclose not in use) to avoid any mal
In case if no binary inputs are configured for indicating circuit
will automatically sets to
“0” (Auto Reclose not in use) to avoid any mal
-
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
. which is started by close command of
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
If the CB gets closed manually, the auto reclose function is
f no binary inputs are configured for indicating circuit
will automatically sets to
“0” (Auto Reclose not in use) to avoid any mal
-
1MDU07212
In case if no binary inputs are configured for indicating circuit
will automatically sets to
-
operation.
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
. which is started by close command of
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
If the CB gets closed manually, the auto reclose function is
f no binary inputs are configured for indicating circuit
will automatically sets to
-
operation.
1MDU07212
In case if no binary inputs are configured for indicating circuit
will automatically sets to
operation.
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
. which is started by close command of
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
If the CB gets closed manually, the auto reclose function is
f no binary inputs are configured for indicating circuit
will automatically sets to
operation.
1MDU07212
REF601 / REJ601
Application Manual
In case if no binary inputs are configured for indicating circuit
will automatically sets to
operation.
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
. which is started by close command of
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
If the CB gets closed manually, the auto reclose function is
f no binary inputs are configured for indicating circuit
will automatically sets to
operation.
1MDU07212
-
REF601 / REJ601
Application Manual
In case if no binary inputs are configured for indicating circuit
will automatically sets to
operation.
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
. which is started by close command of
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
If the CB gets closed manually, the auto reclose function is
f no binary inputs are configured for indicating circuit
will automatically sets to
operation.
-
YN
REF601 / REJ601
Application Manual
In case if no binary inputs are configured for indicating circuit
will automatically sets to
The auto reclose control initiated by above described initiation logic follows
cycle 2 … 4 are initiated with a protection trip signal according the selected
. which is started by close command of
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
If the CB gets closed manually, the auto reclose function is
f no binary inputs are configured for indicating circuit
will automatically sets to
Rev. C
REF601 / REJ601
Application Manual
In case if no binary inputs are configured for indicating circuit
will automatically sets to
cycle 2 … 4 are initiated with a protection trip signal according the selected
. which is started by close command of
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
The auto reclose cycle could get interrupted respective aborted by the signal O
I
f no binary inputs are configured for indicating circuit
will automatically sets to
Rev. C
REF601 / REJ601
Application Manual
will automatically sets to
cycle 2 … 4 are initiated with a protection trip signal according the selected
. which is started by close command of
I cycle. For the start of OI cycle 2 … 4 the CB ready signal is
I
will automatically sets to
REF601 / REJ601
Application Manual
. which is started by close command of

Table of Contents

Other manuals for ABB REJ601

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REJ601 and is the answer not in the manual?

ABB REJ601 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Communication ProtocolIEC 61850, Modbus RTU
Rated Current1/5 A
Operating Time<35 ms
Reset Time<35 ms
CommunicationEthernet, RS-485
Protection DegreeIP20

Related product manuals